2008-04-17 16:11:12 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| |
| 1.PROVIDE A ROOF PLAN SHOWING AREA OF REROOF. |
| |
| 2.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| ADDITION TO THE EVALUATION REPORT SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 3.TWO DIFFERENT NOAS WERE SUBMITTED; POLYGLASS AND |
| GAF, AND THE APPLICATION STATES YOU ARE USING |
| POLYGLASS.PROVIDE TWO IDENTICAL SETS OF ONE PRODUCT. |
| |
| 4.THE POLYGLASS NOA CONTAINS AN ERROR.THIS NOA HAS |
| BEEN REPLACED BY ANOTHER NOA; PLEASE SEE |
| WWW.BUILDINGCODEONLINE.COM OR CONTACT THE MANUFACTURER |
| FOR MORE INFORMATION.THIS NOA CAN BE USED BUT MUST |
| INCLUDE THE ENGINEERING WHICH CORRECTS THE FASTENING |
| ERROR. |
| |
| 5.FOR THE FLAT ROOF, SELECT THE APPROVED ASSEMBLY YOU |
| ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE USING |
| IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| |
| 6.FOR THE FLAT ROOF, SPECIFY THE ENHANCED FASTENING |
| FOR CORNER AND PERIMETER ZONES.THIS IS TO BE EITHER |
| WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED ON |
| LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB SHEET). |
| |
| 7.PLEASE SEE THE NEW POLYGLASS NOA.THERE IS ONE |
| ASSEMBLY WHICH MEETS THE PRESSURE FOR CORNER ZONES AND |
| DOES NOT REQUIRE ENHANCED FASTENING AND ENGINEERING. |
| OTHER SYSTEMS CAN BE USED, BUT THEN COMMENTS 5 AND 6 |
| WOULD APPLY.PLEASE SEE THE NEW POLYGLASS NOA, |
| 07-1030.05. |
| |