2008-12-01 14:26:16 | |
| ** FAILED REVISION** |
| |
| |
| 1) NOTE: PLEASE COORDINATE ALL LIGHTING ON PLANS WITH |
| REVISED LIGHTING PERFORMANCE CALCULATIONS. |
| 13-400.3.A, 13-101.1.1, 13-415.2, 13-415.2.ABC.1.1, |
| .1.2 AND .1.3. |
| PLEASE SEE FOR EXAMPLE THE FIXTURE *T* HAS HAD ALL |
| INFORMATION ON THE FIXTURE LEGEND REMOVED HOWEVER THE |
| PLANS STILL INDICATE MANY *T* FIXTURES. |
| |
| 2) NOTE: PLEASE SEE COMMENTS FROM BUILDING REVIEWER AS |
| THE FLOOR LAYOUTS NEED TO BE COORDINATED. |
| IT IS NOT CLEAR WHICH IS THE CORRECT ONES TO REVIEW. |
| AN EXAMPLE: PLEASE SEE SECOND FLOOR LIFE SAFETY PLAN |
| WHICH CONTAINS AN EXIT SIGN DIRECTLY OCCUPANTS BACK |
| INTO THE BUILDING. THE ELECTRICAL PLANS DO NOT CONTAIN |
| THIS SAME EXIT SIGN. OCCUPANTS ARE NOT TO BE DIRECTED |
| BACK INTO THE BUILDING AND SHOULD FOLLOW THE EGRESS |
| PATH AS DESIGNATED. THIS HAS BEEN CIRCLED ON SHEET |
| A2.12 |
| NFPA- 101, 7.8, 7.9. |
| |
| ** THE ABOVE TWO ARE SOME EXAMPLES WHICH COORDINATION |
| IS NEEDED. |
| FBC 106.1.1 |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |