2008-07-30 14:23:53 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| |
| ****FROM PREVIOUS REVIEW: |
| ******FROM PREVIOUS REVIEWS: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| |
| 13. SHT A7.1.1 ROOM FINISH SCHEDULE FOR ROOM 246. SHOW |
| COMPLIANCE WITH SECTION 1210.1 REQUIREMENT FOR FLOORS |
| TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. CARPET |
| DOES NOT COMPLY WITH THESE REQUIREMENT. PLEASE SHOW |
| COMPLIANCE. |
| ****RESPONSE NOTED, BUT NOT INDICATED ON THE FINISH |
| SCHEDULE. |
| ******RESPONSE NOTED, BUT SHT A7.1.1 HAS NOT BEEN |
| SUBMITTED. |
| |
| 14. OK |
| 15. OK |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| |
| ***********NEW COMMENT*********** |
| |
| 1B. SUBMIT A MINIMUM 2 SETS OF CONSTRUCTION DOCUMENTS |
| REQUIRED. LOOSE SHEETS NOT APPROVED. COMPLETE PLANS NOT |
| SUBMITTED. ONE SET OF OLD (REV 1) PLANS SUBMITTED AND 3 |
| SETS OF LOOSE SHEETS SUBMITTED. FULL SETS OF PLANS NOT |
| SUBMITTED. SECTION 106.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |