2008-08-06 16:23:14 | REVIEW #: 3RD |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| COMMENTS 1 THROUGH 4: OK |
| |
| COMMENT #5: AS INDICATED IN THE WRITTEN RESPONSE FROM |
| THE DESIGN TEAM, A NOTE HAS BEEN ADDED INDICATING HOW |
| SMOKE DAMPERS ARE TO BE CONTROLLED. HOWEVER, THE TYPE |
| AND LOCATION OF SMOKE DETECTORS SHOWN ON ELECTRICAL |
| PLANS TO BE USED TO CONTROL THE DAMPERS DO NOT |
| CORRESPOND WITH THE NOTE ON THE MECHANICAL PLANS. THE |
| SMOKE DETECTORS AS SHOWN ALSO DO NOT MEET THE CRITERIA |
| FOR CONTROLLING ALL SMOKE DAMPERS SHOWN ON THE PLANS AS |
| REQUIRED. PLEASE SEE THE FOLLOWING CODE SECTION WITH |
| OPTIONS LISTED: |
| |
| 607.3.2.1 SMOKE DAMPER ACTUATION METHODS. |
| |
| THE SMOKE DAMPER SHALL CLOSE UPON ACTUATION OF A LISTED |
| SMOKE DETECTOR OR DETECTORS INSTALLED IN ACCORDANCE |
| WITH SECTION 607 OF THIS CODE AND SECTIONS 907.10 AND |
| 907.11 OF THE FLORIDA BUILDING CODE, BUILDING AND ONE |
| OF THE FOLLOWING METHODS, AS APPLICABLE: |
| |
| 1. WHERE A DAMPER IS INSTALLED WITHIN A DUCT, A SMOKE |
| DETECTOR SHALL BE INSTALLED IN THE DUCT WITHIN 5 FEET |
| (1524 MM) OF THE DAMPER WITH NO AIR OUTLETS OR INLETS |
| BETWEEN THE DETECTOR AND THE DAMPER. THE DETECTOR SHALL |
| BE LISTED FOR THE AIR VELOCITY, TEMPERATURE AND |
| HUMIDITY ANTICIPATED AT THE POINT WHERE IT IS |
| INSTALLED. OTHER THAN IN MECHANICAL SMOKE CONTROL |
| SYSTEMS, DAMPERS SHALL BE CLOSED UPON FAN SHUTDOWN |
| WHERE LOCAL SMOKE DETECTORS REQUIRE A MINIMUM VELOCITY |
| TO OPERATE. |
| 2. WHERE A DAMPER IS INSTALLED ABOVE SMOKE BARRIER |
| DOORS IN A SMOKE BARRIER, A SPOT-TYPE DETECTOR LISTED |
| FOR RELEASING SERVICE SHALL BE INSTALLED ON EITHER SIDE |
| OF THE SMOKE BARRIER DOOR OPENING. |
| 3. WHERE A DAMPER IS INSTALLED WITHIN AN UNDUCTED |
| OPENING IN A WALL, A SPOT-TYPE DETECTOR LISTED FOR |
| RELEASING SERVICE SHALL BE INSTALLED WITHIN 5 FEET |
| (1524 MM) HORIZONTALLY OF THE DAMPER. |
| 4. WHERE A DAMPER IS INSTALLED IN A CORRIDOR WALL, THE |
| DAMPER SHALL BE PERMITTED TO BE CONTROLLED BY A SMOKE |
| DETECTION SYSTEM INSTALLED IN THE CORRIDOR. |
| 5. WHERE A TOTAL-COVERAGE SMOKE DETECTOR SYSTEM IS |
| PROVIDED WITHIN AREAS SERVED BY AN HVAC SYSTEM, DAMPERS |
| SHALL BE PERMITTED TO BE CONTROLLED BY THE SMOKE |
| DETECTION SYSTEM. |
| |
| NOTE THAT SPOT-TYPE DETECTORS MAY NOT BE USED TO |
| CONTROL DAMPERS WHICH ARE IN A DUCTED SYSTEM. THEY ARE |
| ONLY FOR DAMPERS IN TRANSFER OPENINGS AS SHOWN IN |
| OPTION #3 ABOVE. PLEASE PROVIDE A CONTROL METHOD WHICH |
| IS IN COMPLIANCE WITH THE METHODS AS PRESCRIBED ABOVE. |
| A SEQUENCE OF PERATIONS MAY BE HELPFUL ON THE PLANS THE |
| DEMONSTRATE COMPLIANCE. PLEASE CORRECT AND RESUBMIT. |
| |
| COMMENTS 6 THROUGH 21: OK |
| |