Plan Review Notes
Plan Review Notes For Permit 08040418
Permit Number 08040418
Review Stop E
Sequence Number 3
Notes
Date Text
2008-08-05 08:08:25 
 **DENIED 3RD REVIEW**
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE SOME
 NEW COMMENTS BASED ON CHANGES MADE TO PLANS AND THE
 NEED FOR COORDINATION.
  
 1) NOTE: PLEASE KNOW THE THREE SETS OF PLANS ARE NOT
 COMPLETE AND ARE MISSING TWO ELECTRICAL SHEETS FROM ONE
 SET. THIS PROJECT ONLY REQUIRES TWO SETS AND UP TO
 THREE MAY BE STAMPED HOWEVER THE THIRD SET NEEDS TO BE
 COMPLETE BEFORE IT COULD BE STAMPED. AS PLANS ARE
 COMING BACK FOR OTHER ELECTRICAL COMMENTS AND
 CORRECTIONS PLEASE EITHER COMPLETE THE THIRD SET OR
 REMOVE FROM SUBMITTING.
  
 2) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 WITH AN INPUT DATA REPORT WHICH COORDINATES WITH PLANS.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE
 REMAINDER OF THIS REVIEW.
 THESE SECTIONS OF CODE APPLY. 13-415.2,
 13-415.2.ABC.1.1,.1.2 AND .1.3. 13-400.A.3, 13-101.1.1
 (AT A MINIMUM).
  
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTING ON PLANS ARE GREATER
 THAN THAT OF THE INFORMATION ON THE IDR.THE 250W
 FIXTURES ARE HIGHER ON PLANS. THE 175W WALL FIXTURES
 ARE HIGHER ON PLANS. IF COMMENTS WERE BASED ON THESE
 FIXTURES ONLY, THIS WOULD NOT CONSTITUTE AS A GROSS
 ERROR AS STATED IN THE CODE. HOWEVER SEE COMMENTS
 BELOW.
  
 FOR EXAMPLE:
 PLEASE SEE FIXTURE LEGEND AS THIS SHOWS TYPE TT
 FIXTURE(S) YET COULD NOT LOCATE ANY OF THESE ON PLANS?
 THE FIXTURE LEGEND LIST THIS FIXTURE IN CONFERENCE ROOM
 BASED ON PLANS THIS WAS NOT SHOWN. PLEASE ALSO SEE THE
 FIXTURE LEGEND LIST 201WATTS FOR THIS TYPE OF FIXTURE
 YET THE IDR DOES LIST ANY 201W FIXTURE OR 200W
 FIXTURE.
  
 FOR EXAMPLE:
 PLEASE SEE SEVERAL LOCATIONS WHICH THE LIGHTING METHOD
 OF CONTROL INDICATE *MAN ON/OFF* YET THIS CAN NOT BE
 POSSIBLE WHEN THE CODE REQUIRES AUTOMATED DEVICES AND
 THE PLANS DO SHOW AUTOMATED DEVICES. ROOMS/AREAS/SPACES
 247,248,260,255 ETC ETC.
 SOME LOCATIONS OF LIGHT FIXTURES ON PLANS SUCH AS *NL*
 FOR NIGHT LIGHTS WOULD STATE THE MANUAL ON/OFF YET
 THERE ARE LOCATIONS IN WHICH THE LIGHTING IS BEING
 AUTOMATICALLY CONTROLLED.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE TWO SPACES 255. EACH SHOWING
 SEPARATE FIXTURE COUNTS AND YET NEITHER COORDINATE WITH
 PLANS. ALSO EACH SHOWING MANUAL ON/OFF.
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE TWO SPACES 219. EACH SHOWING
 SEPARATE FIXTURE COUNTS AND YET NEITHER COORDINATE WITH
 PLANS. ALSO EACH SHOWS MANUAL ON/OFF.
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 202, PLANS SHOW 8 FIXTURES, THE IDR
 SHOWS 6.
  
 FOR EXAMPLE:
 PLEASE SEESPACE 234 WHICH INDICATES 1-67WATT FIXTURE
 YET BASED ON THE FIXTURE NOTED ON PLANS AND THE
 INFORMATION ON THE FIXTURE LEGEND THIS SHOULD BE 134
 WATTS TOTAL.
  
 FOR EXAMPLE: PLEASE SEE SPACE 233 WHICH INDICATES 1-67
 WATT FIXTURE YET BASED ON TYPE OF FIXTURE ON PLANS
 WHICH CORRELATES WITH THE FIXTURE LEGEND THE FIXTURE
 LEGEND CALLS FOR 134WATTS.
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 266 AS PLANS INDICATES 5 OR 6 FIXTURES
 DEPENDING ON SPACE LINES AND THE IDR SHOWS ONLY ONE
 FIXTURE.
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 267 AS THE PLANS SHOWS ONE FIXTURE AND
 THE IDR SHOW MORE. WHICH DESIGN WILL BE USED?
  
 FOR EXAMPLE:
 PLEASE SEE IDR NO SPACE 221 COULD BE LOCATED THEREFORE
 NO FIXTURE AS SHOWN ON PLANS IS IN THE IDR.
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 101 ON PLANS. THE PLANS CALL FOR
 4-TYPE *D* FIXTURES WHICH ARE 52WATTS BASED ON LEGEND
 YET THE IDR DOES NOT CONTAIN ANY 52WATT FIXTURES FOR
 THIS SAME ARE.
 PLEASE SEE SPACE 101 ON PLANS. THE PLANS CALL FOR
 12-TYPE *C* 50.4W FIXTURE BASED ON LEGEND YET THE IDR
 DOES NOT INDICATE ANY OF THESE 50W FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 134.THE IDR SHOWS 28 WATT FIXTURES
 YET THE PLANS DO NOT INDICATE ANY OF THESE FIXTURES?
  
 FOR EXAMPLE:
 PLEASE SEE SPACE 141 AS THE IDR INDICATES 1-67 YET
 PLANS INDICATES 2.
  
 ** AS GIVEN ON PREVIOUS REVIEW THESE ARE EXAMPLES AND
 IS NOT AN EXHAUSTED LIST. THIS CONSTITUTES AS GROSS
 ERRORS BOTH ON FACT THERE ARE MORE FIXTURES AND WATTAGE
 ON PLANS NOT IN THE IDR AND THE IDR SHOWING FIXTURES
 WHICH ARE NOT ON PLANS. THE LIGHTING ON PLANS AND
 CALCULATIONS NEED TO COORDINATE.
  
 3) NOTE: PLEASE INDICATE MAXIMUM TIMES FOR ALL DEVICES.
 PLEASE KNOW THE SYMBOL LEGEND MAY STATE THE MAXIMUM
 TIMES FOR OCCUPANCY SENSOR TYPE DEVICES. THE OVER RIDES
 AS NOTED ON THE LIGHTING CONTROL PLANS DO SHOW THE
 30MINS MAX AS REQUIRED PER 13-415.1.ABC.1.1, .1.2.
  
 4) NOTE: PLEASE SEE ROOM/AREA 248 WHICH SHOWS A FIXTURE
 *E* FOR EMERGENCY HOWEVER BY THE FIXTURE LEGEND NO
 BATTERY BACK UP IS NOTED ON LEGEND.
 ON PREVIOUS REVIEWS THE EMERGENCY FIXTURES HAVE CHANGED
 YET SOME OF THESE ARE STILL IN NEED OF ADDRESSING THE
 MINIMUM FOR THE LIFE SAFETY CODE. RESPONSE MENTIONS A
 NOTE WAS GOING TO BE ADDED TO PLANS FOR THE 100% BACK
 UP OF LUMENS ON FIXTURES HOWEVER THIS NOTE COULD NOT BE
 LOCATED. SINCE THE EMERGENCY LEVELS OF PHOTO-METRICS
 WERE NOT PROVIDED THE NOTES IS REQUIRED OR PROVIDE
 LEVELS UNDER EMERGENCY POWER/BACK UP.
 7.8.1.3, 7.9.1.2, 7.9.2.2
  
 5) NOTE: PLEASE SEE SOME ITEMS N RISER WITH PANEL
 SCHEDULES STILL NEED TO COORDINATE.
 SOME EXAMPLES ARE NOTED.
  
 PLEASE SEE PANEL 1H1. THE MDP LIST 4/0 YET THE RISER
 NOTE FOR THESE FEEDERS INDICATE 3/0.
 PLEASE SEE PANEL 1LEQ WHICH SHOWS 225AMP MCB ON RISER
 YET THE PANEL SHOWS A 200AMP MCB.
 PLEASE SEE 1HL ON RISER WHICH INDICATES A FEED TO PANEL
 2HL YET THE PANEL SCHEDULE FOR 1HL DOES NOT LIST ANY
 BRANCH CIRCUIT TO THE PANEL 2HL.
 310.16, 240.4, 408.4 ETC
 FBC 106.3.5.1.2, 106.1.1 FOR CLARITY AND COORDINATION.
  
 6) NOTE: THE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. EVEN AS THERE ARE SEVERAL CODE SECTIONS
 REPEATED, BASED ON THE CHANGE IN THE METHOD OF ENERGY
 CALCULATIONS THE CALCULATIONS ARE NOT THE SAME. THE
 NEXT REVIEW HOWEVER WILL BE THE THIRD REVIEW OF SAID
 METHOD *A*. THIS FEE HAS NOT BEEN ASSESSED HOWEVER IF
 CALCULATIONS COME BACK IN ON THE NEXT REVIEW WITHOUT
 COORDINATION WITH PLANS THIS REVIEWER WILL HAVE NO
 CHOICE TO ASSESS FEE OF FOUR TIMES THE PLAN REVIEW FEE
 AS STATED IN STATUTE ABOVE. THIS IS A STATUTORY
 REQUIREMENT.
 THIS FEE OF $18,632.79 WOULD BE THE AMOUNT ASSESSED.
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-08-04 17:00:342008-08-04 17:01:34
 NOTES TO FOLLOW ON 8/5