2008-08-05 08:08:25 | |
| **DENIED 3RD REVIEW** |
| |
| ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW |
| ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE SOME |
| NEW COMMENTS BASED ON CHANGES MADE TO PLANS AND THE |
| NEED FOR COORDINATION. |
| |
| 1) NOTE: PLEASE KNOW THE THREE SETS OF PLANS ARE NOT |
| COMPLETE AND ARE MISSING TWO ELECTRICAL SHEETS FROM ONE |
| SET. THIS PROJECT ONLY REQUIRES TWO SETS AND UP TO |
| THREE MAY BE STAMPED HOWEVER THE THIRD SET NEEDS TO BE |
| COMPLETE BEFORE IT COULD BE STAMPED. AS PLANS ARE |
| COMING BACK FOR OTHER ELECTRICAL COMMENTS AND |
| CORRECTIONS PLEASE EITHER COMPLETE THE THIRD SET OR |
| REMOVE FROM SUBMITTING. |
| |
| 2) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS |
| WITH AN INPUT DATA REPORT WHICH COORDINATES WITH PLANS. |
| THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE |
| REMAINDER OF THIS REVIEW. |
| THESE SECTIONS OF CODE APPLY. 13-415.2, |
| 13-415.2.ABC.1.1,.1.2 AND .1.3. 13-400.A.3, 13-101.1.1 |
| (AT A MINIMUM). |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE EXTERIOR LIGHTING ON PLANS ARE GREATER |
| THAN THAT OF THE INFORMATION ON THE IDR.THE 250W |
| FIXTURES ARE HIGHER ON PLANS. THE 175W WALL FIXTURES |
| ARE HIGHER ON PLANS. IF COMMENTS WERE BASED ON THESE |
| FIXTURES ONLY, THIS WOULD NOT CONSTITUTE AS A GROSS |
| ERROR AS STATED IN THE CODE. HOWEVER SEE COMMENTS |
| BELOW. |
| |
| FOR EXAMPLE: |
| PLEASE SEE FIXTURE LEGEND AS THIS SHOWS TYPE TT |
| FIXTURE(S) YET COULD NOT LOCATE ANY OF THESE ON PLANS? |
| THE FIXTURE LEGEND LIST THIS FIXTURE IN CONFERENCE ROOM |
| BASED ON PLANS THIS WAS NOT SHOWN. PLEASE ALSO SEE THE |
| FIXTURE LEGEND LIST 201WATTS FOR THIS TYPE OF FIXTURE |
| YET THE IDR DOES LIST ANY 201W FIXTURE OR 200W |
| FIXTURE. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SEVERAL LOCATIONS WHICH THE LIGHTING METHOD |
| OF CONTROL INDICATE *MAN ON/OFF* YET THIS CAN NOT BE |
| POSSIBLE WHEN THE CODE REQUIRES AUTOMATED DEVICES AND |
| THE PLANS DO SHOW AUTOMATED DEVICES. ROOMS/AREAS/SPACES |
| 247,248,260,255 ETC ETC. |
| SOME LOCATIONS OF LIGHT FIXTURES ON PLANS SUCH AS *NL* |
| FOR NIGHT LIGHTS WOULD STATE THE MANUAL ON/OFF YET |
| THERE ARE LOCATIONS IN WHICH THE LIGHTING IS BEING |
| AUTOMATICALLY CONTROLLED. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THERE ARE TWO SPACES 255. EACH SHOWING |
| SEPARATE FIXTURE COUNTS AND YET NEITHER COORDINATE WITH |
| PLANS. ALSO EACH SHOWING MANUAL ON/OFF. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THERE ARE TWO SPACES 219. EACH SHOWING |
| SEPARATE FIXTURE COUNTS AND YET NEITHER COORDINATE WITH |
| PLANS. ALSO EACH SHOWS MANUAL ON/OFF. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 202, PLANS SHOW 8 FIXTURES, THE IDR |
| SHOWS 6. |
| |
| FOR EXAMPLE: |
| PLEASE SEESPACE 234 WHICH INDICATES 1-67WATT FIXTURE |
| YET BASED ON THE FIXTURE NOTED ON PLANS AND THE |
| INFORMATION ON THE FIXTURE LEGEND THIS SHOULD BE 134 |
| WATTS TOTAL. |
| |
| FOR EXAMPLE: PLEASE SEE SPACE 233 WHICH INDICATES 1-67 |
| WATT FIXTURE YET BASED ON TYPE OF FIXTURE ON PLANS |
| WHICH CORRELATES WITH THE FIXTURE LEGEND THE FIXTURE |
| LEGEND CALLS FOR 134WATTS. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 266 AS PLANS INDICATES 5 OR 6 FIXTURES |
| DEPENDING ON SPACE LINES AND THE IDR SHOWS ONLY ONE |
| FIXTURE. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 267 AS THE PLANS SHOWS ONE FIXTURE AND |
| THE IDR SHOW MORE. WHICH DESIGN WILL BE USED? |
| |
| FOR EXAMPLE: |
| PLEASE SEE IDR NO SPACE 221 COULD BE LOCATED THEREFORE |
| NO FIXTURE AS SHOWN ON PLANS IS IN THE IDR. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 101 ON PLANS. THE PLANS CALL FOR |
| 4-TYPE *D* FIXTURES WHICH ARE 52WATTS BASED ON LEGEND |
| YET THE IDR DOES NOT CONTAIN ANY 52WATT FIXTURES FOR |
| THIS SAME ARE. |
| PLEASE SEE SPACE 101 ON PLANS. THE PLANS CALL FOR |
| 12-TYPE *C* 50.4W FIXTURE BASED ON LEGEND YET THE IDR |
| DOES NOT INDICATE ANY OF THESE 50W FIXTURES. |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 134.THE IDR SHOWS 28 WATT FIXTURES |
| YET THE PLANS DO NOT INDICATE ANY OF THESE FIXTURES? |
| |
| FOR EXAMPLE: |
| PLEASE SEE SPACE 141 AS THE IDR INDICATES 1-67 YET |
| PLANS INDICATES 2. |
| |
| ** AS GIVEN ON PREVIOUS REVIEW THESE ARE EXAMPLES AND |
| IS NOT AN EXHAUSTED LIST. THIS CONSTITUTES AS GROSS |
| ERRORS BOTH ON FACT THERE ARE MORE FIXTURES AND WATTAGE |
| ON PLANS NOT IN THE IDR AND THE IDR SHOWING FIXTURES |
| WHICH ARE NOT ON PLANS. THE LIGHTING ON PLANS AND |
| CALCULATIONS NEED TO COORDINATE. |
| |
| 3) NOTE: PLEASE INDICATE MAXIMUM TIMES FOR ALL DEVICES. |
| PLEASE KNOW THE SYMBOL LEGEND MAY STATE THE MAXIMUM |
| TIMES FOR OCCUPANCY SENSOR TYPE DEVICES. THE OVER RIDES |
| AS NOTED ON THE LIGHTING CONTROL PLANS DO SHOW THE |
| 30MINS MAX AS REQUIRED PER 13-415.1.ABC.1.1, .1.2. |
| |
| 4) NOTE: PLEASE SEE ROOM/AREA 248 WHICH SHOWS A FIXTURE |
| *E* FOR EMERGENCY HOWEVER BY THE FIXTURE LEGEND NO |
| BATTERY BACK UP IS NOTED ON LEGEND. |
| ON PREVIOUS REVIEWS THE EMERGENCY FIXTURES HAVE CHANGED |
| YET SOME OF THESE ARE STILL IN NEED OF ADDRESSING THE |
| MINIMUM FOR THE LIFE SAFETY CODE. RESPONSE MENTIONS A |
| NOTE WAS GOING TO BE ADDED TO PLANS FOR THE 100% BACK |
| UP OF LUMENS ON FIXTURES HOWEVER THIS NOTE COULD NOT BE |
| LOCATED. SINCE THE EMERGENCY LEVELS OF PHOTO-METRICS |
| WERE NOT PROVIDED THE NOTES IS REQUIRED OR PROVIDE |
| LEVELS UNDER EMERGENCY POWER/BACK UP. |
| 7.8.1.3, 7.9.1.2, 7.9.2.2 |
| |
| 5) NOTE: PLEASE SEE SOME ITEMS N RISER WITH PANEL |
| SCHEDULES STILL NEED TO COORDINATE. |
| SOME EXAMPLES ARE NOTED. |
| |
| PLEASE SEE PANEL 1H1. THE MDP LIST 4/0 YET THE RISER |
| NOTE FOR THESE FEEDERS INDICATE 3/0. |
| PLEASE SEE PANEL 1LEQ WHICH SHOWS 225AMP MCB ON RISER |
| YET THE PANEL SHOWS A 200AMP MCB. |
| PLEASE SEE 1HL ON RISER WHICH INDICATES A FEED TO PANEL |
| 2HL YET THE PANEL SCHEDULE FOR 1HL DOES NOT LIST ANY |
| BRANCH CIRCUIT TO THE PANEL 2HL. |
| 310.16, 240.4, 408.4 ETC |
| FBC 106.3.5.1.2, 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 6) NOTE: THE PREVIOUS REVIEW GAVE NOTICE TO FS |
| 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE |
| COMPLIANCE. EVEN AS THERE ARE SEVERAL CODE SECTIONS |
| REPEATED, BASED ON THE CHANGE IN THE METHOD OF ENERGY |
| CALCULATIONS THE CALCULATIONS ARE NOT THE SAME. THE |
| NEXT REVIEW HOWEVER WILL BE THE THIRD REVIEW OF SAID |
| METHOD *A*. THIS FEE HAS NOT BEEN ASSESSED HOWEVER IF |
| CALCULATIONS COME BACK IN ON THE NEXT REVIEW WITHOUT |
| COORDINATION WITH PLANS THIS REVIEWER WILL HAVE NO |
| CHOICE TO ASSESS FEE OF FOUR TIMES THE PLAN REVIEW FEE |
| AS STATED IN STATUTE ABOVE. THIS IS A STATUTORY |
| REQUIREMENT. |
| THIS FEE OF $18,632.79 WOULD BE THE AMOUNT ASSESSED. |
| |
| |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |