2008-06-30 13:31:25 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| |
| 1. THE REFERENCE STANDARD HAS BEEN CORRECTED. HOWEVER, |
| SUPPORTING DOCUMENTATION FOR USE OF THE IAQ PROCEDURE |
| WAS NOT PROVIDED AS REQUESTED IN PREVIOUS REVIEW |
| COMMENT #1. PROVIDE SUPPORTING DOCUMENTATION IN |
| ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 6.3.2 AND FBCB |
| 106.1.2. |
| |
| 2. THE 40X16 SUPPLY DUCT FROM AHU 1-2 IS PENETRATING A |
| FIRE RESISTANCE RATED WALL AT THE ELEVATOR EQUIPMENT |
| ROOM #155 WITH NO PROTECTION. SHOW HOW THIS DUCT |
| PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM |
| 607.5. |
| |
| 3 AND 4: OK |
| |
| 5. SMOKE DAMPERS HAVE BEEN SHOWN IN REQUIRED LOCATIONS |
| IN THE CORRIDOR. HOWEVER, THE DAMPER ACTUATION METHOD |
| INDICATED IN KEY NOTE #1 DOES NOT MEET THE REQUIREMENTS |
| OF FBCM 607.5.4.1. GIVEN THE HVAC DESIGN AND |
| CONFIGURATION OF THE BUILDING, IT APPEARS THAT UNDER |
| FBCM 607.5.4.1, OPTIONS 1, 4 OR 5 WOULD BE APPLICABLE. |
| THE USE OF ONE DUCT SMOKE DETECTOR AT THE AHU DOES NOT |
| MEET ANY OF THE OPTIONS LISTED UNDER THIS SECTION |
| BECAUSE IT IS NOT WITHIN 5 FEET OF THE DAMPERS AND IT |
| DOES NOT QUALIFY AS TOTAL-COVERAGE SMOKE DETECTION. |
| ADDITIONALLY, THE 10X10 AIR TRANSFER OPENING FSD SHALL |
| BE ACTUATED BY OPTION 3 OR 4. THE OTHER FIRE/SMOKE |
| DAMPERS NOT ASSOCIATED WITH THE CORRIDOR SHALL BE |
| ACTUATED BY METHOD 1 OR 3 AS APPROPRIATE FOR THE |
| APPLICATION. EXAMPLE: |
| THE FIRE/SMOKE DAMPERS IN THE WALL WEST OF |
| |
| 6. OK EXCEPT, PLEASE VERIFY THAT ONE 30X12 TRANSFER AIR |
| OPENING IS SUFFICIENT TO RETURN ALMOST 4000 CFM FROM |
| THE MAIN LOBBY, RECEPTION AND FORMAL CONFERENCE AREAS |
| IN ACCORDANCE WITH FBCM 601.4 AND FBCB 106.1.2. |
| |
| 7 THROUGH 10: OK |
| |
| 11. SMOKE DAMPERS ARE SHOWN ON PLANS AS REQUIRED. |
| PLEASE SEE COMMENT #5 REGARDING DAMPER ACTUATION |
| REQUIREMENTS. |
| |
| 12. NOTHING IS SHOWN ON THE AHU SCHEDULE REGARDING |
| AUXILIARY DRAIN PROTECTION. PLEASE SHOW COMPLIANCE WITH |
| FBCM 307.2.3. |
| |
| 13. OK. SEE COMMENT #5 FOR SMOKE DAMPER ACTUATION |
| REQUIREMENTS. |
| |
| 14 THROUGH 19: OK |
| |
| 20. MECHANICAL PORTIONS OF THE ENERGY CALCULATIONS ARE |
| OK. |
| |
| 21. OK |
| |
| NOTE: THE PRINTING OF MECHANICAL FLOOR PLANS, M1.01 AND |
| M2.01, ARE OF POOR QUALITY. MANY OF THE SMALL NUMBERS |
| RELATED TO DUCT SIZES AND AIR TERMINAL DESIGNATIONS |
| ILLEGIBLE. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE IN |
| ACCORDANCE WITH FBCB 106.1.1. WHEN RE-SUBMITTING, |
| PLEASE ENSURE THAT ALL RELEVANT INFORMATION ON FLOOR |
| PLANS IS CLEAR AND LEGIBLE. |
| |