2008-05-03 11:12:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SUBMIT EXISTING FLOOR PLANS FOR 1ST & 2ND FLOOR AS
 WELL AS A DEMO PLAN SHOWING THE LOCATION ALL PLUMBING
 PIPES TO DEMO'D. SECTION 106.1.2.
  
 2. A PLUMBING DEMO PERMIT IS REQUIRED. (SEE PERMIT #
 08010573 WHICH INDICATES A COMPLETE INTERIOR
 DEMOLITION). SECTIONS 106.1.2 & 704.5.
  
 3. SHTS A2.2.1 & A2.2.2 DEMO NOTES #4 & #5 WERE NOT
 FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 4. PER TABLE 403.1 3 DRINKING FOUNTAINS ARE REQUIRED.
 HI/LOW DRINKING ARE CONSIDERED 2 FIXTURES IF THEY HAVE
 SEPARATE TRAPS & SUPPLIES. IF THE HI/LOW DRINKING
 FOUNTAINS HAVE ONLY ONE TRAP AND ONE WATER SUPPLY THEN
 ONLY 2 FIXTURES ARE SHOWN. PLEASE INDICATE ON THE RISER
 DIAGRAMS THE TRAP AND SUPPLY REQUIREMENTS. SECTIONS
 106.3.5.1.3, 606.2(1) & 1002.1.
  
 5. SHTS A 2.2.1 & A2.2.2 ROOMS 148, 269 & 271 INDICATES
 JANITOR ROOMS. PLEASE INDICATE IF THERE ARE OR WERE
 MOP/SERVICE SINKS IN THESE ROOMS. ALSO INDICATE IF THE
 SINKS WERE DELETED. PLEASE CLARIFY. SECTION 106.1.2.
  
 6. SHTS A2.2.1 & A2.2.2 INDICATES THE TOILET ROOM
 DETAILS CAN BE FOUND ON SHT A4.1.1 DETAILS 1, 2 & 3.
 THE DETAILS WERE NOT FOUND ON SHT A4.1.1. PLEASE
 CLARIFY/CORRELATE. SECTION 106.1.1.
  
 7. SHTS A2.2.1 & A2.2.3 DO NOT SHOW THE BREAK ROOM SINK
 AS SHOWN ON SHT P1.01. PLEASE SHOW THE SINK ON ALL
 FLOOR PLANS AS THERE APPEARS TO BE A CONFLICT WITH THE
 REQUIRED CLEAR FLOOR SPACE AND THE FURNITURE. SECTIONS
 106.1.1 & 11-4.16.2.
  
 8. SUBMIT DETAILS AND ELEVATIONS FOR THE TOILET ROOM
 AND THE BATHROOM SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 & 11-4.23 WITH ALL
 SUBSECTIONS AND FIGURES. INDICATE THE SIZE OF THE
 SHOWER. SEE SECTION 11-4.21.2 & FIG 35(A).
  
 9. SUBMIT A DETAIL AND AN ELEVATION FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS AND FIGURES. FORWARD APPROACH REQUIRED AND
 CABINET DOORS ARE NOT APPROVED IN THE CLEAR FLOOR
 SPACE.
  
 10. SUBMIT A DETAIL AND ELEVATION FOR THE ACCESSIBLE
 DRINKING FOUNTAINS SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS & FIGURES AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 11. SHT A4.1.2 TYPICAL TOILET ACCESSORIES INDICATE THE
 GRAB BARS AT 3'1". PER SECTION 11-4.16.4 & FIG 11-29
 GRAB BARS SHALL BE INSTALLED 33"-36" ABOVE THE FLOOR.
 PLEASE CORRECT DETAIL.
  
 12. SHT A7.1.1 ROOM FINISH SCHEDULE FOR ROOM 112. SHOW
 COMPLIANCE WITH SECTION 1210.2 REQUIREMENT FOR WALLS
 WITHIN 2' OF THE W/C SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE TO A HEIGHT OF 4' ABOVE THE FLOOR.
 PAINTED GWB DOES NOT COMPLY THE THE REQUIRED FOR A
 "HARD" SURFACE. PLEASE SHOW COMPLIANCE.
  
 13. SHT A7.1.1 ROOM FINISH SCHEDULE FOR ROOM 246. SHOW
 COMPLIANCE WITH SECTION 1210.1 REQUIREMENT FOR FLOORS
 TO HAVE A SMOOTH, HARD, NONABSORBENT SURFACE. CARPET
 DOES NOT COMPLY WITH THESE REQUIREMENT. PLEASE SHOW
 COMPLIANCE.
  
 14. SHT A7.1.1 ALL EXISTING TOILET ROOMS INDICATED AS
 EXISTING SHALL COMPLY WITH SECTIONS 1210.1 & 1210.2 AS
 WELL.
  
 15. SHT P1.01 PLUMBING DEMO NOTES 1, 2 & 5 INDICATE THE
 DEMO'D PIPING TO BE CAPPED AND SEALED BELOW THE FLOOR.
 PER SECTION 704.5 IN THE REMOVAL OF ANY DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. ALL DEMO'D
 PIPING SHALL BE CAPPED OFF WITHIN 2FT OF THE BRANCH
 LINE OR BUILDING DRAIN LINE. PLEASE INDICATE ON PLANS.
  
 16. SUBMIT AN ISOMETRIC SANITARY RISER DIAGRAM FOR THE
 BREAK ROOM SINK, AND DRINKING FOUNTAINS SHOWING ALL
 PIPE SIZES, TRAPS, VENTS ETC. SECTIONS 106.3.5.1.3 &
 701.1 AS WELL AS TABLES 710.1(1) & 710.1(2), 901.2.1 &
 1002.1.
  
 17. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM FOR THE
 BREAK ROOM SINK, DRINKING FOUNTAINS, DISHWASHER ETC
 SHOWING ALL PIPE SIZES, VALVES AND , WHERE REQUIRED,
 WATER HAMMER ARRESTORS PER 604.9, (ANY ICE MAKERS,
 DISHWASHERS ETC), INSTALLED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. SECTIONS
 106.3.5.1.3, 601.1, 604 - TABLE 604.5 & PDI-WH 201.
  
 18. SHT P3.01 TRAP PRIMERS ARE INDICATED TO THE SHOWER
 DRAINS ON THE SANITARY RISER DIAGRAM BUT ARE NOT SHOWN
 ON THE WATER RISER DIAGRAM. PLEASE CLARIFY & CORRELATE.
 SECTIONS 106.1.1 & 1002.4.
  
 19. SHT P3.01 THE SANITARY RISER DIAGRAM IS IDENTIFIED
 ASTHE DOMESTIC WATER RISER DIAGRAM AND THE WATER
 RISER DIAGRAM IS IDENTIFIED AS THE SANITARY WASTE &
 VENT RISER DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 20. SHT P4.01 SUBMIT CALCULATIONS FOR THE EXPANSION
 TANK FOR ELECTRIC WATER HEATER - EWH-1. ON-LINE
 CALCULATIONS CONFLICT WITH EXPANSION TANK SIZE
 SUBMITTED ON THE PLANS. (SEE ATTACHED SHEET). SECTION
 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  