Plan Review Notes
Plan Review Notes For Permit 08040418
Permit Number 08040418
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-06 10:47:37REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG M0.01: DESIGN CRITERIA SCHEDULE CALLS FOR
 VENTILATION TO BE DESIGNED PER ASHRAE 62.1-2007. THIS
 IS NOT A REFERENCED STANDARD UNDER THE 2004 FBC. THE
 CORRECT STANDARD IS ASHRAE 62.1-2004 IN ACCORDANCE WITH
 FBCM 403.4 AND FBCM CHAPTER 15. VENTILATION SYSTEMS
 SHALL BE DESIGNED IN ACCORDANCE WITH THIS STANDARD OR
 FBCM SECTION 403. IF ASHRAE 62.1-2004 IS USED, DECLARE
 ON PLANS WHETHER THE VENTILATION RATE (VR) OR INDOOR
 AIR QUALITY (IAQ) PROCEDURE IS USED IN ACCORDANCE WITH
 SECTION 6.1.
  
 ALSO, PROVIDE SUPPORTING DOCUMENTATION. IF USING THE VR
 PROCEDURE IS USED, PROVIDE OUTDOOR AIR CALCULATIONS
 WITH SPACE-BY-SPACE OCCUPANCY CLASSIFICATIONS, OCCUPANT
 LOADS, OUTDOOR AIR REQUIRED AND OUTDOOR AIR PROVIDED IN
 ACCORDANCE WITH SECTION 6.2. IF THE IAQ PROCEDURE IS
 USED, PROVIDE DOCUMENTATION AS REQUIRED BY SECTION
 6.3.2.
  
 2. PG M1.01 AND M2.01: THE LOCATIONS OF RATED WALL
 ASSEMBLIES FROM LIFE SAFETY PAGES A2.1.1AND A2.1.2 WERE
 USED FOR REVIEW OF MECHANICAL FLOOR PLANS TO CHECK FOR
 PROPERLY PROTECTED DUCT PENETRATIONS OF WALL
 ASSEMBLIES. IT SHOULD BE NOTED THAT ARCHITECTURAL FLOOR
 PLANS AND LIFE SAFETY PLANS ARE NOT COORDINATED WITH
 REGARD TO THE LOCATIONS OF RATED WALL ASSEMBLIES.
 REVIEW OF DUCT PENETRATION WILL BE BASED ON THE LIFE
 SAFETY PLANS. PLEASE MAKE SURE ANY CHANGES RELATED TO
 WALL ASSEMBLIES ARE COORDINATED BETWEEN ARCHITECTURAL,
 LIFE SAFETY AND MECHANICAL PLANS.
  
 3. PG M1.01: FLOOR PLAN SHOWS A 20X12 UNPROTECTED DUCT
 PENETRATION OF THE 1-HOUR RATED WALL BETWEEN TRAINING
 AREA 145 AND BREAKROOM 143. SHOW HOW THIS PENETRATION
 IS TO BE PROTECTED IN ACCORDANCE WITH FBCM 607.5.
  
 4. PG M1.01: THERE IS A FIRE DAMPER SHOWN IN THE 8 INCH
 ROUND DUCT PENETRATING THE WALL BETWEEN W.H. CLOSET 117
 AND MEN?S LOCKER/SHOWER 114. THIS WALL IS NOT SHOWN TO
 HAVE A FIRE RESISTANCE RATING ON THE LIFE SAFETY PLAN
 OR THE ARCHITECTURAL FLOOR PLAN. FIRE DAMPERS ARE TO BE
 INSTALLED IN RATED ASSEMBLIES IN ACCORDANCE WITH THEIR
 LISTING AND MANUFACTURER?S INSTALLATION INSTRUCTIONS
 PER FBCM 607.2. PLEASE COORDINATE FLOOR PLANS WITH
 MECHANICAL PLANS, SHOWING PROTECTED PENETRATIONS ONLY
 AT RATED ASSEMBLIES.
  
 5. PG M1.01: LIFE SAFETY PLAN SHOWS CORRIDOR 144 TO BE
 1-HOUR FIRE RESISTANCE RATED. THREE OF THE FIVE DUCT
 PENETRATIONS IN THIS CORRIDOR ARE REQUIRED TO BE
 PROTECTED WITH SMOKE DAMPERS IN ADDITION TO THE FIRE
 DAMPERS ALREADY SHOWN ON THE PLANS IN ACCORDANCE WITH
 FBCM 607.5.4 AND FBCB 715.3.3. THE OTHER TWO
 PENETRATIONS (12 INCH ROUND DUCT FEEDING SERVER ROOM
 147) ARE EXEMPT FROM THE SMOKE DAMPER REQUIREMENT IN
 ACCORDANCE WITH FBCM 607.5.4(3). ALSO, SHOW HOW THESE
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBCM 607.5.4.1.
  
 6.PG M1.01 AND M2.01: MECHANICAL FLOOR PLAN INDICATES
 THAT THIS DESIGN IS USING A PLENUM CEILING WITH OPEN
 END DUCTS BACK TO AHU-1-1 AND AHU-2-1. THERE ARE SOME
 AREAS OF THE FLOOR PLAN WHERE RATED WALL ASSEMBLIES,
 WHICH ARE CONSTRUCTED FROM FLOOR TO DECK OR FLOOR TO
 ROOF, WILL IMPEDE THE FLOW OF RETURN AIR BACK TO THE
 OPEN END DUCTS. THESE AREAS WOULD INCLUDE THE FOLLOWING
 EXAMPLES:
 MAIN LOBBY 101
 RECEPTION AREA 102
 FORMAL CONFERENCE 103
 CORRIDOR 144
 TRAINING AREA 145
 LOBBY 201
 CONFERENCE 202
 HALLWAY 203
 CORRIDOR 263
  
 PLEASE CHECK THE ENTIRE FLOOR PLAN TO ENSURE THAT THESE
 AND POSSIBLE OTHER AREAS ARE PROVIDED WITH BALANCED
 RETURN AIR FLOW IN ACCORDANCE WITH FBCM 601.4. PLEASE
 ENSURE THAT ANY ADDED DUCT PENETRATIONS OR AIR TRANSFER
 OPENINGS ARE PROTECTED IN ACCORDANCE WITH FBCM 607.5
 AND FBCB 710.7 WHERE APPLICABLE.
  
 7. PG M1.01 AND M2.01: PLAN SHOWS DUCTS FOR EF-1, EF-2
 AND GRV-1 PENETRATING THE FLOOR/CEILING ASSEMBLY
 BETWEEN 1ST AND 2ND FLOORS. SHOW THESE PENETRATIONS TO
 BE PROTECTED IN ACCORDANCE WITH FBCM 607.6.
  
 8. PG M2.01: FLOOR PLAN SHOWS A 62X16 UNPROTECTED DUCT
 PENETRATION AT THE FIRE-RESISTANCE RATED WALL BETWEEN
 HALLWAY 203 AND FAX/PRINTING 204. SHOW HOW THIS
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
  
 9. PG M2.01: FLOOR PLAN SHOWS A 10 INCH ROUND
 UNPROTECTED DUCT PENETRATION AT THE FIRE-RESISTANCE
 RATED WALL BETWEEN FAX/PRINTING 204 AND CONFERENCE 202.
 SHOW HOW THIS PENETRATION IS TO BE PROTECTED IN
 ACCORDANCE WITH FBCM 607.5. ALSO, THERE IS A FIRE
 DAMPER SHOWN IN THIS SAME DUCT LINE IN THE 7 INCH ROUND
 DUCT BUT IT IS NOT LOCATED AT THE WALL ASSEMBLY. PLEASE
 CORRECT BY COORDINATING MECHANICAL WITH ARCHITECTURAL
 AND LIFE SAFETY PLANS, ENSURING FIRE DAMPERS ARE
 INSTALLED ONLY AT RATED WALL OR FLOOR/CEILING
 ASSEMBLIES IN ACCORDANCE WITH FBCM 607.2.
  
 10. PG M2.01: FLOOR PLAN SHOWS A FIRE DAMPER IN THE 10
 INCH ROUND DUCT FEEDING VAV -1 IN HALLWAY 203. THERE IS
 NO WALL ASSEMBLY WHERE THE FIRE DAMPER IS LOCATED ON
 PLANS. PLEASE CORRECT BY COORDINATING MECHANICAL WITH
 ARCHITECTURAL AND LIFE SAFETY PLANS, ENSURING FIRE
 DAMPERS ARE INSTALLED ONLY AT RATED WALL OR
 FLOOR/CEILING ASSEMBLIES IN ACCORDANCE WITH FBCM
 607.2.
  
 11. PG M2.01: LIFE SAFETY PLAN SHOWS CORRIDOR 263 TO BE
 1-HOUR FIRE RESISTANCE RATED. THE FOUR DUCT
 PENETRATIONS IN THIS CORRIDOR ARE REQUIRED TO BE
 PROTECTED WITH SMOKE DAMPERS IN ADDITION TO THE FIRE
 DAMPERS ALREADY SHOWN ON THE PLANS IN ACCORDANCE WITH
 FBCM 607.5.4 AND FBCB 715.3.3. ALSO, SHOW HOW THESE
 SMOKE DAMPERS ARE TO BE ACTUATED IN ACCORDANCE WITH
 FBCM 607.5.4.1.
  
 12. SHOW MEANS AND LOCATION OF AUXILIARY OR SECONDARY
 DRAIN PROTECTION ON ALL APPLIANCES WITH COOLING COILS
 IN ACCORDANCE WITH FBCM 307.2.3.
  
 13. NO MEANS OF VENTILATION OR AIR CONDITIONING IS
 SHOWN ON PLANS FOR THE ELEVATOR MACHINE ROOM. SHOW HOW
 THIS ROOM IS TO BE VENTILATED OR CONDITIONED IN
 ACCORDANCE WITH FBCB 3006.2
  
 14. NO ROOF MECHANICAL PLAN WAS PROVIDED. SHOW LAYOUT
 OF ROOF WITH LOCATIONS OF EFS AND GRV. SHOW COMPLIANCE
 WITH FBCM 401.5 AND 401.6. ALSO, SHOW HOW ROOFTOP
 EXHAUST FANS ARE TO BE ACCESSED FOR SERVICE. WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT EXCEEDING
 16 FEET, SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT
 APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE
 FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND
 APPLIANCES? LEVEL SERVICE SPACE IN ACCORDANCE WITH FBCM
 306.5.
  
 15. PG M5.01: THE RATIO OF THE FAN SYSTEM POWER TO THE
 SUPPLY FAN AIRFLOW RATE (MAIN FAN) OF EACH HVAC SYSTEM
 AT DESIGN CONDITIONS SHALL NOT EXCEED THE ALLOWABLE FAN
 SYSTEM POWER SHOWN IN TABLE 410.1.ABC.1.1.1. IF OPTION
 2 OR 3 OF THIS SECTION IS CLAIMED, PLEASE PROVIDE
 SUPPORTING DOCUMENTATION AND CALCULATIONS. EXAMPLE:
 AHU-1-2 SHOWS 5,100 CFM WITH A 10 HP MOTOR. THIS GIVES
 A RATIO OF 1.96 HP PER 1,000 CFM, WHICH IS IN EXCESS OF
 THAT ALLOWED BY THE TABLE. PLEASE CHECK ALL FANS.
  
 16. PG M6.01: AHU CONDENSATE DRAIN DETAIL, THIS DETAIL
 DOES NOT CORRESPOND WITH THE MANUFACTURER?S
 INSTRUCTIONS. CONDENSATE DRAINS SHALL BE TRAPPED AS
 REQUIRED BY THE EQUIPMENT OR APPLIANCE MANUFACTURER IN
 ACCORDANCE WITH FBCM 307.2.4. A COPY OF THE CONDENSATE
 TRAP DETAIL FROM THE MANUFACTURER IS ATTACHED TO THESE
 COMMENTS. PROVIDE A DETAIL WHICH CORRESPONDS WITH THE
 MANUFACTURER?S REQUIREMENTS OR DEFER TO THE
 MANUFACTURER?S INSTRUCTIONS.
  
 17. PG M6.02: ROOF MOUNTED FAN DETAIL, NOTE CALLS FOR
 DETAIL ON ARCHITECTURAL AND STRUCTURAL PLANS. NO SUCH
 DETAIL COULD BE FOUND TO SHOW HOW CURBS ARE TO BE
 ATTACHED TO STRUCTURE. PLEASE PROVIDE MISSING
 INFORMATION, SHOWING HOW CURB IS TO BE ATTACHED TO
 WITHSTAND ANTICIPATED WIND LOADS IN ACCORDANCE WITH
 FBCM 301.13. ALSO, PROVIDE ADDITIONAL DETAIL SHOWING
 THE NUMBER AND SIZE OF FASTENERS TO BE USED TO ATTACH
 FANS AND GRV TO CURBS TO WITHSTAND ANTICIPATED WIND
 PRESSURES. IN ADDITION, SHOW GRV AND FANS THEMSELVES
 ARE DESIGNED TO RESIST ANTICIPATED WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13.
  
 18. PG M7.01: PROVIDE OPTIMUM START CONTROLS AS
 REQUIRED IN ACCORDANCE WITH FBCB 13-407.1.ABC.2.4.2.
  
 19. PG M7.03 WATER TEMPERATURE RESET CONTROLS ARE
 REQUIRED IN ACCORDANCE WITH FBCB 13-411.1.ABC.1.3.
  
 20. ENERGY CALCULATIONS: A METHOD A COMPLIANCE FORM HAS
 BEEN SUBMITTED. HOWEVER, THIS IS NOT AN ACCEPTABLE
 METHOD FOR THIS PROJECT. NONRESIDENTIAL BUILDINGS THAT
 ARE PERMITTED PRIOR TO DESIGN COMPLETION OR WHICH WILL
 BE FINISHED IN SECTIONS AT A TIME AFTER CONSTRUCTION OF
 THE SHELL SHALL COMPLY WITH EITHER METHOD B OR C OF
 SUBCHAPTER 13-4 OF THE CODE PRIOR TO GRANTING OF A
 PERMIT TO BUILD IN ACCORDANCE WITH FBCB 13-101.1.6. THE
 ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS TIME
 DUE TO THE INCORRECT METHOD BEING SUBMITTED. PLEASE
 SUBMIT A METHOD B OR C COMPLIANCE FORM FOR REVIEW.
  
 21. HANSON PROFESSIONAL SERVICES SHALL PROVIDE A VALID
 ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION
 NUMBER ON EACH SHEET OF MECHANICAL PLANS IN THE TITLE
 BLOCK IN ACCORDANCE WITH FAC RULE 16G15-23.002.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH
 EXPLANATION AS TO HOW EACH COMMENT WAS ADDRESSED AND
 WHERE THE RELEVANT INFORMATION CAN BE FOUND. ALSO
 PLEASE RETURN ONE SET OF OLD/VOIDED PLANS FOR
 REFERENCE.
  