Plan Review Notes
Plan Review Notes For Permit 08040418
Permit Number 08040418
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-05-15 17:17:09*****DENIED*****
  
  
 1.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SHOW THE LOCDATION OF THE 2A10BC RATED FIRE
 EXTINGUISHERS ON THE LIFE SAFETY SHEETS.
  
 7.INCLUDE ON THE APPROPIATE MECHANICAL AND/OR FIRE
 ALARM SHEET THAT:DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM.
  
 8.PROVIDE THE PRESCRIPTIVE STRENGHT FOR THE NEW
 HANDRAIL/GUARDRAILS TO BE INSTALLED.
  
 9.PLANS MENTION: 1) A FIRE PUMPAND2) A GENERATOR.
 PLEASE SUBMIT SPECIFICATIONS AND/OR CUT SHEETS FOR
 THESE DEVICES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722