Plan Review Notes For Permit 08040418 |
Permit Number |
08040418 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-15 17:17:09 | *****DENIED***** | | | | | | 1.THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 5.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS | | IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 6.SHOW THE LOCDATION OF THE 2A10BC RATED FIRE | | EXTINGUISHERS ON THE LIFE SAFETY SHEETS. | | | | 7.INCLUDE ON THE APPROPIATE MECHANICAL AND/OR FIRE | | ALARM SHEET THAT:DUCT SMOKE DETECTORS SHALL INITIATE | | A GENERAL FIRE ALARM. | | | | 8.PROVIDE THE PRESCRIPTIVE STRENGHT FOR THE NEW | | HANDRAIL/GUARDRAILS TO BE INSTALLED. | | | | 9.PLANS MENTION: 1) A FIRE PUMPAND2) A GENERATOR. | | PLEASE SUBMIT SPECIFICATIONS AND/OR CUT SHEETS FOR | | THESE DEVICES. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|