Plan Review Notes
Plan Review Notes For Permit 08040418
Permit Number 08040418
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-01 15:12:25** DENIEDREVIEW **
  
 **** IMPORTANT****
 PLEASE SEE COMMENTS BELOW: AS THERE IS INFORMATION,
 DOCUMENTS, PLANS ETC WHICH ARE NOT SUBMITTED SOME ITEMS
 FOR CODE COMPLIANCE CAN NOT BE REVIEWED AT THIS TIME.
 PLEASE SEE THE LIST OF COMMENT BELOW BASED ON PLANS AND
 DOCUMENTS WHICH WERE SUBMITTED. IT IS IMPORTANT TO
 UNDERSTAND THAT DUE TO MUCH NEED FOR CHANGES FOR CODE
 COMPLIANCE AND ITEMS WHICH CAN NOT BE REVIEWED THERE
 MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 1) NOTE: PLEASE SEE THE PLANS SUBMITTED SHALL CONTAIN
 THE LATEST ADOPTED CODES UNDER THE FLORIDA BUILDING
 CODE ALONG WITH STATUTORY ADOPTED CODES. PLEASE SEE THE
 FOLLOWING SHALL BE STATED ON PLANS. SOME CODES BELOW
 ARE BEING REQUESTED TO BE STATED AND SHOWN ON
 ELECTRICAL AS WELL AS COVER SHEETS.
 2004 FBC W/2007
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
 2005 NFPA-70
  
 PLEASE KNOW SOME SHEETS REFERENCE A FIRE PUMP AS NOTED
 ON E6.05 SEE NOTES WITH RESPECT TO ANY FIRE PUMP.
 PLEASE SEE THERE ARE SEVERAL SHEETS IN WHICH CODES ARE
 BEING REFLECTED FROM THE 1999 NFPA-70 (NEC).
 FOR EXAMPLE:
 PLEASE SEE E0.03 AND 0.04, NOTES FOR GROUNDING IS
 STATING 250.26 FOR SEPARATELY DERIVED SYSTEMS. THIS
 CHANGED IN THE 2002 AND 2005 NEC.
 PLEASE SEE THESE SAME SHEETS FOR NOTES ON WIRING WHICH
 REFLECTS 370.20/21 HOWEVER THIS IS NO LONGER IN EFFECT
 FOR EQUIPMENT AS STATED. THE 2002 AND 2005 WERE BOTH
 CHANGED AND THE SECTIONS 370 OF THE NEWER CODES
 ACTUALLY REFLECT THE CABLEBUS.
 ** THE IS ONLY A COUPLE OF EXAMPLES AND IS NOT AN
 EXHAUSTED LIST OF LOCATIONS. THIS IS GIVEN AS A BENEFIT
 ONLY AND IS IN NO WAY ALL POSSIBLE LOCATIONS.
  
  
 2) NOTE: PLEASE BE SURE THE ADDRESS TO THE LOCATION OF
 THIS PROJECT IS LISTED ON ALL TITLE BLOCKS ON ALL
 SHEETS.
 PLEASE SEE FAC 61G1-16.004, 61G15-23.002, FBC ADMIN
 SECTION 106.5.
  
 3) NOTE: PLEASE SEE THE COLOR CODING SHOWN ON E0.03
 SHALL BE BROWN, PURPLE AND YELLOW FOR 277/480V
 SYSTEMS.
 ORANGE AS STATED IN NEC 110.15 IS ONLY FOR A
 *HIGH-LEG*. THE 277/480V IS NOT A HIGH-LEG.
 PLEASE KNOW AS THE NEC DOES NOT PROVIDED COLOR CODING
 FOR THIS PARTICULAR SYSTEM THE CITY OF WEST PALM BEACH
 ALONG WITH ALL OF PALM BEACH COUNTY HAD TECHNICAL
 AMENDMENTS WHICH WERE IN EFFECT FOR MORE THAN 30 YEARS.
 EVEN THOUGH THIS TECHNICAL AMENDMENT IS NO LONGER IN
 EFFECT IN KEEPING WITH COORDINATION, SAFETY AND
 CONTINUITY OF OTHER WIRING WHICH ALREADY EXISTS IN THIS
 AHJ PLEASE ADJUST.
 90.4
  
 4) NOTE: PLEASE SEE E6.05 WHICH SHOWS GROUNDING DETAIL
 WHICH MENTIONS TO FIRE PUMP YET NO FIRE PUMP,
 ELECTRICAL FOR FIRE PUMP ETC WAS LOCATED ON ANY OTHER
 SHEET(S).
 IF A FIRE PUMP IS INDEED GOING TO BE INSTALLED PLEASE
 SUBMIT ALL INFORMATION INCLUDING MANUFACTURES SPECS/CUT
 SHEETS FOR SUCH SYSTEM/UNIT.
 PLEASE SEE 695 OF NFPA-70 AND ALL OF 2003 NFPA-20.
  
 5) NOTE: PLANS ARE SPECIFICALLY CALLING FOR A *LIFE
 SAFETY* AND *EMERGENCY* TRANSFER SWITCHES YET THE PLANS
 DO NOT SHOW ANY GENERATOR.
 THERE IS NO ELECTRICAL ON THE EMERGENCY SIDE ON EITHER
 OF THE TRANSFER SWITCHES. IF THIS IS A TRUE LIFE SAFETY
 REQUIRED SYSTEM UNDER 700 OR 701, THEN THE GENERATOR
 AND ALL OTHER REQUIRED SHALL BE IN THE DESIGN FOR
 MINIMUM CODE COMPLIANCE UNDER NFPA-101, 20, 110, 70
 ETC.
 PLEASE KNOW AS NO INFORMATION, SPECS, MANUFACTURES CUT
 SHEETS, ETC WAS SUBMITTED NO REVIEW OF *MINIMUM* CODE
 COMPLIANCE CAN BE DONE AT THIS TIME. IF THERE IS A
 LEGALLY REQUIRED SYSTEM OR LIFE SAFETY SYSTEM, PLEASE
 IDENTIFY AND INCLUDE ALL FOR MINIMUM CODE COMPLIANCE.
 IF LOADS ARE ONLY GOING TO BE OPTION STAND-BY THEN
 PLEASE ADJUST ALL PLANS ETC FOR CODE COMPLIANCE. PLEASE
 CAREFULLY REVIEW NEC 700,701 AND 702 FOR ACTUAL LOADS.
 *** IMPORTANT**
 PLEASE KNOW IF A GENERATOR IS GOING TO BE INSTALLED THE
 PLANS FOR ALL OTHER TRADES SHALL BE REVISED TO INCLUDE
 ANY SUCH UNIT.
 PLEASE BE SURE TO INCLUDE ELEVATIONS ON
 SITE/BUILDING/STRUCTURAL SHEETS.
 PLEASE BE SURE TO INCLUDE ON SITE PLANS FOR
 CIVIL/ZONING REVIEWS.
 PLEASE BE SURE TO INCLUDE SCREENING AS REQUIRED BY
 ZONING.
 PLEASE BE SURE TO INCLUDE STRUCTURAL SLAB DETAILS FOR
 UNIT, TIE DOWNS ETC.
 PLEASE BE SURE TO INCLUDE SIZE OF FUEL TANK AS
 DEPENDING ON SIZE THERE MAY BE NEEDS FOR REVIEW AND
 STAMP BY DERM.
  
 THE ITEMS LISTED ABOVE ARE NOT AN EXHAUSTED LIST AS
 THERE WILL BE COMMENTS FROM OTHER TRADES. THESE NOTES
 WILL BE FORWARDED TO OTHER TRADES.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR
 BOTH TRANSFER SWITCHES. 90.7, 110.3, 700, 701, OR 702.
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE KNOW AS THE BUILDING IS NOT BEING DONE AS A
 WHOLE BUILDING AND STILL INCLUDED SHELL SPACES METHOD
 *A* MAY NOT BE USED.
 PLEASE SEE 13-400.3.B, 13-400.3.C, 13-101.1.3,
 13-101.1.6 ETC.
 PLEASE KNOW EVEN AS METHOD *A* WAS SUBMITTED IN THE
 INFORMATION SHOWN ON THE INPUT DATA REPORT AND
 CALCULATIONS DOES NOT CORRELATE WITH PLANS.
 PLEASE KNOW THE INPUT DATA REPORT WILL BE NOTED AS IDR
 FOR REMAINDER OF THIS COMMENT.
 PLEASE KNOW THAT ALL INFORMATION ON PLANS SHALL
 COORDINATE WITH THE IDR. ALL COMPONENTS OF THE BUILDING
 FOR ENERGY EFFICIENCIES SHALL BE INCLUDED. SOME
 EXAMPLES WILL BE GIVEN BELOW FOR ITEMS WHICH ARE
 MISSING
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH ONLY SHOWS A TOTAL OF FOUR
 LIGHT FIXTURES. HOW IS THIS POSSIBLE WHEN THE IDR
 CLEARLY REQUIRES THE TYPES OF LUMINAIRES, THE NUMBER OF
 *EACH* OF THOSE LUMINAIRES, THE WATTAGE ON EACH OF
 THOSE LUMINAIRIES ETC.
 BASED ON THE IDR SUBMITTED THIS DOES NOT MEET THE
 *MINIMUM* REQUIRED.
 FOR EXAMPLE:
 PLEASE ONCE AGAIN SEE THE IDR WHICH SHOWS ONLY 16-42
 WATT FIXTURES. HOW IS THIS POSSIBLE WHEN THE PLANS
 CLEARLY SHOW THE *Q* FIXTURE ALONE BEING 75W. PLEASE
 KNOW THAT *ALL* EXTERIOR LIGHTING IS REQUIRED BY CODE
 TO BE FIGURED INTO THE IDR FOR EXTERIOR CALCULATIONS
 AND ALLOWANCES.
 THE FIXTURES ON THE FIXTURE LEGEND ALSO INCLUDE OTHER
 EXTERIOR LIGHTS HOW THESE ARE NOT SHOWN.
  
 ** THIS IS ONLY TWO EXAMPLES. ONE FOR INTERIOR AND ONE
 FOR EXTERIOR AND THIS IS NOT AN EXHAUSTED LIST. THESE
 EXAMPLES ARE GIVEN AS A BENEFIT ONLY AND ARE NO WAY ALL
 ITEMS ON THE IDR WHICH DO NOT COORDINATE WITH THE
 SUBMITTED PLANS.
 ** PLEASE SEE COMMENTS FROM OTHER TRADES AS THERE ARE
 OTHER BUILDING COMPONENTS WHICH DO NOT COORDINATE.
 PLEASE SEE SECTIONS NOTED ABOVE ALONG WITH 13-415.2,
 13-415.2.ABC.1.1, .1.1, AND .1.3. (ETC)
  
 ** AS THERE ARE SEVERAL ITEMS NOT YET COMPLETE ON PLANS
 THERE MAY VERY WELL BE ADDITIONAL COMMENTS ON THE
 FOLLOWING REVIEW.
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
 PLEASE SUBMIT MORE INFORMATION ON PLANS FOR LIGHTING
 CONTROLS. THERE IS A NOTE ON E0.01 WHICH STATES ALL
 LIGHTING SHALL MEET CHAPTER 13, HOWEVER QUOTING THE
 CODE IN LIEU OF ACTUAL MINIMUM DESIGN IS NOT
 PERMITTED.
 PLEASE SEE AS NO SITE PARKING LOT LIGHTING WAS SHOWN ON
 PLANS COMPLIANCE WITH .1.4 AS NOTED ABOVE CAN NOT
 VERIFIED. ONCE PLANS ARE COMPLETE FOR ALL LIGHTING
 REVIEW OF ALL SYSTEMS ETC WILL BE REVIEWED.
 PLEASE SEE SOME EXAMPLES WILL BE GIVEN BELOW HOWEVER
 THESE ARE IN NO WAY AN EXHAUSTED LIST.
 FOR EXAMPLE:
 PLEASE SEE SEVERAL OUTSIDE OFFICES WHICH APPEAR TO SHOW
 A STANDARD LIGHT SWITCH. HOW DOES THIS DEVICE WORK AS
 AN OVER RIDE OR WITH THE SYSTEM AS PROPOSED?
 FOR EXAMPLE:
 PLEASE SEE SECTIONS OF CODES NOTED AS EACH FLOOR IS
 REQUIRED TO CONTAIN A SEPARATE SYSTEM IF LIGHTING
 CONTROL PANELS ARE TO BE INSTALLED.
 FOR EXAMPLE:
 PLANS NOTE THAT ALL LIGHTING SHALL BE TURNED OFF AND
 CODE DOES REQUIRE THIS. PLEASE VERIFY LIGHTING CONTROLS
 IN STAIRS AND OTHER LOCATIONS WHICH DO NOT APPEAR TO
 SHOW ANY CONTROLS.
 PLEASE SEE LIFE SAFETY CODE 101, 7.8.1.2.2 AND FBC
 1016.1 FOR REQUIRED FAIL SAFE ON FOR EGRESS LIGHTING.
 FOR EXAMPLE:
 PLEASE KNOW THERE IS NOTHING IN THE CODE WHICH PERMITS
 NIGHT LIGHTS. THIS AHJ WILL PERMIT SOME NIGHT LIGHTS
 FOR SECURITY AS LONG AS LEVEL DOES NOT EXCEED 1 FT
 CANDLE AVG ON EGRESS PATHS.
 FOR EXAMPLE:
 PLEASE SEE NO OUTSIDE LIGHTING AND CONTROLS SHOWN FOR
 OTHER FIXTURES. SOME FIXTURES ON BUILDING ARE NOTED AS
 ON PHOTO-SENSOR HOW NOT ALL. THERE IS A LIGHTING
 CONTACTOR DETAIL HOWEVER NO ALL LIGHTING LISTED.
  
 AS NOTED THIS IS NOT AN EXHAUSTED LIST AND IS GIVEN AS
 A BENEFIT ONLY.
  
 8) NOTE: PLEASE SUBMIT COMPLETED LOAD CALCULATIONS FOR
 PANELS AND SERVICE.
 NEC 220, 220.12, 220.14, 220.42, 220.44 ETC
 PLEASE SEE THAT ALL CONTINUOUS LOADS SHALL BE SHOWN AT
 125%. 215.3, 230.42
  
 9) NOTE: PLEASE SEE THAT THE LOCATION OF THE MAIN FOR
 THE BUILDING IS NOT ACCEPTABLE TO THIS AHJ. THE
 LOCATION OF THE MAIN IS NOT LOCATED AT THE NEAREST
 POINT OF ENTRANCE IN AN EMERGENCY. FIRE DEPARTMENT
 PERSONNEL MUST HAVE A QUICK AND READY ACCESS TO THE
 MAIN LOCATION WITHOUT A SUBSTANTIAL TRAVEL DISTANCE
 THROUGH A BUILDING WHICH MAY BE ON FIRE.
 PLEASE RELOCATED ACCESS, ADD ACCESS, ADD MAIN ETC. THIS
 MAY BE GONE OVER WITH THIS AHJ.
 230.70,71, 72, 76, 79 ETC
  
 10) NOTE: PLEASE SEE 110.26C2 AS THE DOOR SWING ON THE
 MAIN ELECTRICAL ROOM SHALL NOT SWING IN.
 THE DOOR IS REQUIRED TO SWING OUT AND IS REQUIRED TO
 CONTAIN PANIC HARDWARE ETC.
 PLEASE KNOW THE ROOM, EQUIPMENT; DOOR ETC WILL ALL
 DEPEND ON DESIGN TO COMPLY WITH NOTE #9 ABOVE. IN ANY
 CASE 1200AMP EQUIPMENT WILL BE REQUIRED TO CONTAIN
 DOOR(S) WITH OUT-SWING.
  
 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 EGRESS STAIRS UNDER NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SE NFPA-101 7.8.1.3, 7.9.2.2
 FAC 61G15-33.004
  
 12) NOTE: PLANS CONTAIN A NOTE ON RISER FOR GF
 PROTECTION OF MAIN HOWEVER PLEASE BE SURE TO INCLUDE
 SPECIFIC INFORMATION ON THE MDP/MAIN.
 240.13, 230.95.
 PLEASE KNOW IF THERE ARE ANY REQUIRED LIFE SAFETY
 SYSTEMS, SELECTIVE COORDINATION PER 240.13.
  
 13) NOTE: PLEASE SEE RISER WHICH SHOWS 800AMP OVER
 CURRENT PROTECTION ON PANEL 1-HEQ WHICH IS A 400AMP
 PANEL. HOW IS THIS POSSIBLE?
 110.9, 90.4, 240.4 ETC
  
 14) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS ALL
 OF THESE PANELS ON THE SECONDARY SIDE OF THE
 TRANSFORMERS REQUIRE MAINS.
 THERE ARE SEVERAL CODE SECTIONS AND SOME EXAMPLES OF
 WHICH PANELS ARE GIVEN BELOW.
 1L1,
 1LEQ,
 1LLS. ETC
 PLEASE SEE 240.21, 240.4, 310.16, 408.36 ETC
 THIS IS NOT AN EXHAUSTED EXAMPLE.
  
 15) NOTE: PLEASE SEE THAT ALL CONDUCTORS ON THE
 SECONDARY SIDE OF TRANSFORMER SHALL TERMINATE IN OVER
 CURRENT PROTECTION AS NOTED ABOVE IN NOTE #14. THESE
 CONDUCTORS SHALL ALSO BE RATED FOR THAT OCP.
 FOR EXAMPLE:
 PLEASE SEE THE CONDUCTORS GOING INTO *1L1* WHICH ARE
 SHOWN AS 500MCM. THESE CONDUCTORS PER 110.14, 110.3,
 AND 310.16 ARE ONLY RATED FOR 380AMPS.
 IN THIS PARTICULAR SCENARIO YOU MAY NOT GO TO THE NEXT
 SIZE UP WHEN THE OCP LISTED PER 240.6 DOES NOT
 COORDINATE WITH THE CONDUCTOR RATING.
 MUST MEET OR EXCEED OCP ON THE SECONDARY SIDE. (MIN
 600MCM)
  
 16) NOTE: PLEASE BE SURE TO COMPLETE NOTES ON PLANS PER
 13-413.1.ABC.2.1 AND .2.2.
 THE NOTES ON ELECTRICAL SHEET COVER PAGE DOES PARTIALLY
 LIST THIS HOWEVER NOT ALL.
 PLEASE KNOW THIS WAS CONFIRMED WITH DCA/FBC AS THE
 EXACT WORDING AS LISTED IN THE CODE WAS THE INTENT TO
 HAVE LISTED ON PLANS.
  
 17) NOTE: PLEASE SEE PANELS *1L1 AND 1L12* ON RISER
 APPEARS TO BE SHOWN AS A TWO SECTION PANEL HOWEVER PER
 THE PANEL SCHEDULE THESE ARE TWO SEPARATE PANELS AND
 EACH PANEL DOES NOT CONTAIN THE SAME PANEL RATING. ONE
 IS LISTED AS 400AMP AND THE OTHER AS 225AMP. PLEASE
 COORDINATE AND ADJUST.
 110.3,90.7 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 18) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR NEW OR
 EXISTING SITE LIGHTS.
 PLANS MENTION THIS HOWEVER AT THIS TIME THESE CAN NOT
 BE CONFIRMED.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO LIGHTS,
 CALCULATIONS ETC.
 FBC 106.3.5.1.2
  
 19) NOTE: PLEASE SEE SITE ELECTRICAL PLANS SPECIFICALLY
 CALL FOR A GROUND RING AND TO SEE DETAIL ON E6.05 YET
 E6.05 DOES NOT SHOW ANY GROUND RING AS PART OF THE
 GROUNDING ELECTRODE SYSTEM DETAIL.
 PLEASE VERIFY ??
 250.50
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 20) NOTE: PLEASE VERIFY SERVER ROOM. IS THIS AN IT ROOM
 AS DEFINED IN NFPA-75, NFPA-70?
 PLEASE SEE 645.1 AND .4.
 PLANS SHOW RATED WALLS, FIRE DAMPERS, A/C , FM 200
 SYSTEM ETC HOWEVER NO SHUT OFF PER 645.10 WAS LOCATED
 ON PLANS.
 PLEASE KNOW THERE ARE SEVERAL UNANSWERED QUESTIONS WITH
 RESPECT TO THIS ROOM.
  
 21) NOTE: PLEASE SEE NFPA-70 620.23 FOR REQUIRED
 DEDICATED CIRCUITS IN MACHINE ROOM.
 FOR EXAMPLE:
 PLEASE SEE THE LIGHTING CIRCUIT FEEDING THIS ROOM
 CURRENTLY ALSO FEEDS SEVERAL OTHER LIGHTING FIXTURES
 OUTSIDE OF THIS ROOM WHICH IS NOT PERMITTED BY CODE.
 PLEASE KNOW THIS IS NOT A NEW CODE. PLEASE ADJUST
 PLANS.
  
 22) NOTE: PLEASE SEE 620.24 WHICH REQUIRE DEDICATED
 CIRCUITS FOR PIT/HOIST-WAY LIGHTS AND RECEPTACLES.
 PLEASE SEE PLANS AS THE CIRCUIT WHICH FEEDS THE PIT GFI
 WHICH IS *1L1-30* ALSO FEEDS MECHANICAL ROOM
 RECEPTACLES, RECEPTION AREA ETC.
 PLEASE ADJUST; THIS IS NOT A NEW CODE.
  
 23) NOTE: PLEASE SEE THE ELEVATOR MACHINE ROOM PER FBC
 3006.2 IS REQUIRED TO CONTAIN SEPARATE CONDITIONING.
 PLEASE SEE COMMENTS FROM MECHANICAL REVIEWER AS THIS
 WILL AFFECT ELECTRICAL PLANS AS NOTED.
 ** THIS IS BEING GIVEN FOR INFORMATION ONLY.
  
 24) NOTE: PLEASE SEE CONDUCTORS ON RISER FOR
 TRANSFORMER *1TN* WHICH SHOWS 200AMP OCP ON MDP ON 1/0
 CONDUCTORS WHICH ARE ONLY RATED FOR 150AMPS PER
 310.16.
 PLEASE CORRECT AND ADJUST.
 THIS IS NOT WHAT IS SHOWN ON MDP SCHEDULE. MDP SCHEDULE
 INDICATES 150AMP BREAKER AND NOT 200AMP.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION.
  
 25) NOTE: PLEASE BE SURE TO COMPLETE THE CERTIFICATION
 SHEETS ON THE SUBMITTED ENERGY CALCULATIONS.
 THE COVER SHEET WAS SIGNED, DATED AND SEALED HOWEVER
 THIS SHOULD BE ON THE CERTIFICATION SHEETS.
 PLEASE ALSO SEE OTHER INFORMATION REQUIRE ON THESE SAME
 SHEETS SUCH AS OWNER/AGENT SIGNATURE IS REQUIRED. FBC
 13-103.1.1.1, FAC 61G15-23.002
  
 26) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIMES ON
 OVER RIDE DEVICES. PLEASE SEE THE LOCATIONS OF EACH
 OVER RIDE SHALL BE LOCATED SO THE OCCUPANT CAN VISUALLY
 SEE THE LIGHTING IN WHICH THEY ARE CONTROLLING. THERE
 ARE EXCEPTIONS ON THE CODE HOWEVER NO INFORMATION COULD
 BE LOCATED ON PLANS ON HOW *PILOTS/INDICATORS LIGHTS*
 WILL BE USED OR INSTALLED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
  
 27) NOTE: PLEASE SEE SYMBOL LEGEND MENTIONS THE USE OF
 WHAT APPEARS TO BE A SPRING WOUND TIMER FOR SOME
 LOCATIONS.
 PLEASE SEE FBC 11-4.27.4 WHICH DOES NOT PERMIT THE USE
 OF THESE DEVICES.
 THIS MAY ALSO BE LIMITED TO SOME LOCATIONS AS PERMITTED
 BY CODE.
  
 28) NOTE: PLEASE SUBMIT AND PROVIDE AN ENLARGED
 ELECTRICAL ROOM PLAN TO SCALE FOR THE MAIN ELECTRICAL
 ROOM.
 BASED ON THE EQUIPMENT SHOWN AND MINIMUM CLEARANCES
 REQUIRED IN 110.26 THERE IS CONCERN OVER THE SIZE OF
 THE ROOM AND EQUIPMENT AS SHOWN.
 PLEASE SEE MANUFACTURES MINIMUM CLEARANCE FOR
 TRANSFORMER, VENTILATION ETC.
 PLEASE SEE 110.26, 450.9, 450.13, 450.21 ETC.
  
 29) NOTE: PLEASE SEE SHEET E1.03 WHICH APPEARS TO USE A
 SQUARE BOX WITH A C INSIDE AS ONE OF THE SYMBOLS LOCATE
 AT DOOR. THIS SYMBOL ON E0.02 MENTIONS THIS IS A
 LIGHTING CONTACTOR. WHAT IS THIS?
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 30) NOTE: PLEASE SEE SYMBOLS ON THE SHEET E1.03 AS
 THERE ARE DEVICES WHICH APPEAR TO PARTIAL FIRE
 DEVICES.
 FOR EXAMPLE:
 PLEASE SEE STAIR #2 WHICH SHOWS A PARTIAL FIRE DEVICE.
 THIS IS ONE EXAMPLE:
  
 31) NOTE: PLEASE INCLUDE MAXIMUM HEIGHT FOR ALL DEVICES
 PER ADA 11-4.27.
 PLEASE PLACE NOTE ON PLANS TO INCLUDE.
  
 32) NOTE: PLEASE CLARIFY THE *SPECIAL OUTLET* IN THE
 BREAK-ROOM KITCHEN AREA. 1L12, 8, 10,12.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 33) NOTE: PLEASE PLACE NOTES ON PLANS FOR THE FOLLOWING
 PER FBC SECTION 2704.1 WHICH REQUIRES BONDING OF METAL
 FRAMING MEMBERS.
 METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT
 GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE
 THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE
 NATIONAL ELECTRIC CODE, TABLE 250.122. FOR THE PURPOSE
 OF THIS SECTION, A GROUNDED METAL OUTLET BOX ATTACHED
 TO THE FRAMING SHALL BE PERMITTED.
  
 34) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS
 ABOVE, ONE ROLL OF PLANS ARE BEING RETAINED BY THIS
 OFFICE ALONG WITH ONE SET OF ENERGY CALCULATION
 SUBMITTED.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]