Plan Review Notes
Plan Review Notes For Permit 08040418
Permit Number 08040418
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-03 15:31:09BUILDING PLAN REVIEW
 PERMIT: 08040418
 ADD: 1 HARVARD CIRCLE
 CONT: SUFFOLK CONSTRUCTION
 TEL: (561)644-6405
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) ON THE HEADER STRIP FOR THE ARCHITECTURAL SHEETS
 PLEASE PROVIDE THE LOCATION OF THE PROJECT.
 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 XX - STATE PROJECT NAME & LOCATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL INCLUDE
 THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 3) FLORIDA ENERGY CODE PROJECT SUMMARY SHEET INDICATES
 THE USE OF METHOD A, WHERE THERE ARE UNKNOWNS ON SHEET
 A2.2.1 AND A2.2.2 FUTURE EXPANSION AREAS.
 PLEASE REVIEW SECTION 13-400.0C.4 FOR WHICH FORM MAY BE
 USED. NOTE LEVEL 3 ALTERATIONS INCLUDE ANY WORK
 COMPLETED WITHIN ANY 12 ?MONTH PERIOD.2004 EXISTING
 BUILDING CODE 305.1.
  
 4) ENERGY CERTIFICATION SHEET IS LEFT UNSEALED. EACH OF
 THE DISCIPLINES WOULD NEED TO SEAL FOR THEIR PORTION OF
 WORK THEY ARE CERTIFYING. TRUE THERE SHOULD BE ONLY ONE
 SEAL PER PAGE SO FOR EXAMPLE JOEVEN VALENZUELA WOULD
 SIGN AND SEAL A INDIVIDUAL SHEET FOR THE LIGHTING AND
 ELECTRICAL TOM CAOOELLIN WOULD ALSO DO THE SAME FOR THE
 MECHANICAL AND PLUMBING AS WELL AS STEVEN KNIGHT FOR
 ARCHITECT OF RECORD.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 5) ENERGY INPUT DATA REPORT SHEET# 3 FOR WALLS
 INDICATES THE EXTERIOR WALLS ARE TO HAVE A R-VALUE OF
 12.5, SHEET A7.2.3 INDICATES DETAIL# 1 AS AN EXTERIOR
 WALL BUT NOT R-VALUE IS PROVIDED FOR THE INSULATION.
 THE WINDOW AND EXTERIOR WALL (EFIS) PERMIT 08010752
 INDICATES THE STO INSULATION BOARD IS TO BE 1? THICK
 BUT I CAN NOT FIND IN THE NOA SUPPLIED A R-VALUE NOR ON
 LINE FROM THE STO WEB-SITE. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS TO COMPLY WITH THE ENERGY CODE AND
 SECTION 13-402.1.
  
 6) ENERGY INPUT DATA REPORT SHEET# 5 FOR DOORS THIS
 SHEET INDICATES THERE ARE A TOTAL OF (7) 3?-0?X 7?-0?
 SOLID CORE FLUSH DOORS WHEREAS SHEET A7.2.1 INDICATES
 THERE ARE (13) 3?-0?X7?-0? DOORS. THE OTHER ISSUE IS ON
 THIS SHEET FOR DOOR INFORMATION AND FRAME ALL EXISTING
 DOOR INFORMATION INDICATES EXISTING, PLEASE PROVIDE
 TYPE OF MATERIALS FOR DOOR AND FRAME, UNDER REMARKS YOU
 CAN INDICATE EXISTING DOORS.
 PLEASE REVISIT AND CORRECT THE INPUT DATA REPORT
 SECTION 13-403.
  
 7) SHEET A2.2.1 NEW WORK NOTES:
 7A) NOTE A INDICATES NEW HANDRAILS IN STAIRWAYS 1,2& 3.
 THERE IS NO MENTION OF NEW HANDRAILS FOR EITHER THE
 ENTRY RAMP NOR THE 2 FRONT ENTRY STAIRS. THIS SAME
 SHEET INDICATES A PORTION OF THE MAIN LOBBY AND
 EXTERIOR DECK ARE GOING TO BE RAISED WITH A
 NEW DECK. THIS NEW DECK WILL INCREASE THE STAIRS WITH
 AT LEST ONE NEW RISER AND WILL
 CREATE A STEEPER RAMP SINCE THE START OF THE RAMP AND
 MID LANDING ARE FIXED POINTS.
 7A)(1) PLEASE PROVIDE THE ELEVATION CHANGE FROM THE
 EXISTING SURFACE TO THE NEW FINISH, WILL THIS NEW RISER
 BE CONSISTENT WITH THE OTHER RISERS IN EACH OF THE
 EXTERIOR STAIRS? 1009.3.1.SHEET A4.1.1 INDICATE TREAD
 BUT NOT THE RISER HEIGHT?
 7A)(2) PLEASE PROVIDE DETAILS FOR THE NEW HANDRAILS FOR
 THE 2 EXTERIOR STAIRS. 1009.14 & 11-4.9.4. A4.1.1
 DETAIL 1 THE END OF THE HANDRAIL APPEARS TO BE GREATER
 THAN 27? FROM GRADE. SEE 11-4.4.1 AND FIGURE 19. 7A)(3)
 PLEASE PROVIDE THE NEW SLOPE FOR THE EXISTING RAMP,
 PLEASE SEE 11-4.8.2.
 7A)(4) PLEASE PROVIDE DETAILS FOR THE NEW HAND RAIL FOR
 THE RAMP. 11-4.8.5.
 7A((5) A4.1.1 ENLARGED LOBBY AREA INDICATES ON THE
 STAIRS THE HANDRAIL EXTENSION BEING A TOTAL OF 1?-2?
 AWAY FROM THE LAST TREAD. SEE 11-4.9.4(2).
 7A)(6) A4.1.1 DETAIL 1 INDICATES THE HANDRAIL TO BE 1
 ?? SQUARE TUBING. 11-4.9.4 HANDRAILS SHALL COMPLY WITH
 SECTION 11-4.26 PLEASE PROVIDE THAT THE SQUARE TUBING
 PROVIDES THE EQUIVALENT GRIPPING SURFACE AS 11-4.9.4.
  
 7B) NOTE (B) INDICATES THAT THE NO. 2 STAIRWAY IS OPEN?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 7C) THE ELEVATOR MACHINE ROOM IS MISSING RATING OF SOME
 WALLS AND DOOR SEE 3006.4.
  
 8) SHEET A8.1.1 WALL DETAIL 100 TYPO PLEASE CORRECT THE
 STUD GAUGE THICKNESS TO REFLECT THAT OF UL 465. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 9) SHEET A2.2.2 NOTES K & M BOTH INDICATE THROUGH
 PENETRATIONS TO THE FIRST FLOOR BUT THE MECHANICAL
 PLANS DO NOT INDICATE DAMPERS. SEE FBCB 716.1. JIM
 WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.