2008-05-03 15:31:09 | BUILDING PLAN REVIEW |
| PERMIT: 08040418 |
| ADD: 1 HARVARD CIRCLE |
| CONT: SUFFOLK CONSTRUCTION |
| TEL: (561)644-6405 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 2) ON THE HEADER STRIP FOR THE ARCHITECTURAL SHEETS |
| PLEASE PROVIDE THE LOCATION OF THE PROJECT. |
| 61G1-16.004 FL. ADMIN. CODE. PLANS PREPARED BY A |
| REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| MUST: |
| - STATE THE FIRM NAME, ADDRESS AND TELEPHONE NUMBER |
| - STATE THE FIRM LICENSE NUMBER |
| XX - STATE PROJECT NAME & LOCATION |
| - STATE DATE PREPARED |
| - INCLUDE AN ORIGINAL SIGNATURE AND DATED SEAL INCLUDE |
| THE PRINTED NAME OF THE |
| ARCHITECT SEALING THE PLANS |
| |
| 3) FLORIDA ENERGY CODE PROJECT SUMMARY SHEET INDICATES |
| THE USE OF METHOD A, WHERE THERE ARE UNKNOWNS ON SHEET |
| A2.2.1 AND A2.2.2 FUTURE EXPANSION AREAS. |
| PLEASE REVIEW SECTION 13-400.0C.4 FOR WHICH FORM MAY BE |
| USED. NOTE LEVEL 3 ALTERATIONS INCLUDE ANY WORK |
| COMPLETED WITHIN ANY 12 ?MONTH PERIOD.2004 EXISTING |
| BUILDING CODE 305.1. |
| |
| 4) ENERGY CERTIFICATION SHEET IS LEFT UNSEALED. EACH OF |
| THE DISCIPLINES WOULD NEED TO SEAL FOR THEIR PORTION OF |
| WORK THEY ARE CERTIFYING. TRUE THERE SHOULD BE ONLY ONE |
| SEAL PER PAGE SO FOR EXAMPLE JOEVEN VALENZUELA WOULD |
| SIGN AND SEAL A INDIVIDUAL SHEET FOR THE LIGHTING AND |
| ELECTRICAL TOM CAOOELLIN WOULD ALSO DO THE SAME FOR THE |
| MECHANICAL AND PLUMBING AS WELL AS STEVEN KNIGHT FOR |
| ARCHITECT OF RECORD. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G15-23.002 ENGINEERS |
| FL ADMIN CODE 61G16.003 ARCHITECTS |
| |
| 5) ENERGY INPUT DATA REPORT SHEET# 3 FOR WALLS |
| INDICATES THE EXTERIOR WALLS ARE TO HAVE A R-VALUE OF |
| 12.5, SHEET A7.2.3 INDICATES DETAIL# 1 AS AN EXTERIOR |
| WALL BUT NOT R-VALUE IS PROVIDED FOR THE INSULATION. |
| THE WINDOW AND EXTERIOR WALL (EFIS) PERMIT 08010752 |
| INDICATES THE STO INSULATION BOARD IS TO BE 1? THICK |
| BUT I CAN NOT FIND IN THE NOA SUPPLIED A R-VALUE NOR ON |
| LINE FROM THE STO WEB-SITE. PLEASE PROVIDE ADDITIONAL |
| INFORMATION AS TO COMPLY WITH THE ENERGY CODE AND |
| SECTION 13-402.1. |
| |
| 6) ENERGY INPUT DATA REPORT SHEET# 5 FOR DOORS THIS |
| SHEET INDICATES THERE ARE A TOTAL OF (7) 3?-0?X 7?-0? |
| SOLID CORE FLUSH DOORS WHEREAS SHEET A7.2.1 INDICATES |
| THERE ARE (13) 3?-0?X7?-0? DOORS. THE OTHER ISSUE IS ON |
| THIS SHEET FOR DOOR INFORMATION AND FRAME ALL EXISTING |
| DOOR INFORMATION INDICATES EXISTING, PLEASE PROVIDE |
| TYPE OF MATERIALS FOR DOOR AND FRAME, UNDER REMARKS YOU |
| CAN INDICATE EXISTING DOORS. |
| PLEASE REVISIT AND CORRECT THE INPUT DATA REPORT |
| SECTION 13-403. |
| |
| 7) SHEET A2.2.1 NEW WORK NOTES: |
| 7A) NOTE A INDICATES NEW HANDRAILS IN STAIRWAYS 1,2& 3. |
| THERE IS NO MENTION OF NEW HANDRAILS FOR EITHER THE |
| ENTRY RAMP NOR THE 2 FRONT ENTRY STAIRS. THIS SAME |
| SHEET INDICATES A PORTION OF THE MAIN LOBBY AND |
| EXTERIOR DECK ARE GOING TO BE RAISED WITH A |
| NEW DECK. THIS NEW DECK WILL INCREASE THE STAIRS WITH |
| AT LEST ONE NEW RISER AND WILL |
| CREATE A STEEPER RAMP SINCE THE START OF THE RAMP AND |
| MID LANDING ARE FIXED POINTS. |
| 7A)(1) PLEASE PROVIDE THE ELEVATION CHANGE FROM THE |
| EXISTING SURFACE TO THE NEW FINISH, WILL THIS NEW RISER |
| BE CONSISTENT WITH THE OTHER RISERS IN EACH OF THE |
| EXTERIOR STAIRS? 1009.3.1.SHEET A4.1.1 INDICATE TREAD |
| BUT NOT THE RISER HEIGHT? |
| 7A)(2) PLEASE PROVIDE DETAILS FOR THE NEW HANDRAILS FOR |
| THE 2 EXTERIOR STAIRS. 1009.14 & 11-4.9.4. A4.1.1 |
| DETAIL 1 THE END OF THE HANDRAIL APPEARS TO BE GREATER |
| THAN 27? FROM GRADE. SEE 11-4.4.1 AND FIGURE 19. 7A)(3) |
| PLEASE PROVIDE THE NEW SLOPE FOR THE EXISTING RAMP, |
| PLEASE SEE 11-4.8.2. |
| 7A)(4) PLEASE PROVIDE DETAILS FOR THE NEW HAND RAIL FOR |
| THE RAMP. 11-4.8.5. |
| 7A((5) A4.1.1 ENLARGED LOBBY AREA INDICATES ON THE |
| STAIRS THE HANDRAIL EXTENSION BEING A TOTAL OF 1?-2? |
| AWAY FROM THE LAST TREAD. SEE 11-4.9.4(2). |
| 7A)(6) A4.1.1 DETAIL 1 INDICATES THE HANDRAIL TO BE 1 |
| ?? SQUARE TUBING. 11-4.9.4 HANDRAILS SHALL COMPLY WITH |
| SECTION 11-4.26 PLEASE PROVIDE THAT THE SQUARE TUBING |
| PROVIDES THE EQUIVALENT GRIPPING SURFACE AS 11-4.9.4. |
| |
| 7B) NOTE (B) INDICATES THAT THE NO. 2 STAIRWAY IS OPEN? |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 7C) THE ELEVATOR MACHINE ROOM IS MISSING RATING OF SOME |
| WALLS AND DOOR SEE 3006.4. |
| |
| 8) SHEET A8.1.1 WALL DETAIL 100 TYPO PLEASE CORRECT THE |
| STUD GAUGE THICKNESS TO REFLECT THAT OF UL 465. 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 9) SHEET A2.2.2 NOTES K & M BOTH INDICATE THROUGH |
| PENETRATIONS TO THE FIRST FLOOR BUT THE MECHANICAL |
| PLANS DO NOT INDICATE DAMPERS. SEE FBCB 716.1. JIM |
| WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |