Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop E
Sequence Number 5
Notes
Date Text
2009-03-24 11:17:20PLANS ROUTED TO BUILDING AS THE THIRD SET DOES NOT
 CONTAIN ANY BUILDING STAMPS
2009-03-24 11:15:18** PLANS REDLINED **
  
 THE ELECTRICAL SYSTEM/RISER NEEDS TO BE VERIFIED. THE
 ORIGINAL PLANS CALLED FOR A LIFE SAFETY/ EMERGENCY
 TRANSFER SWITCH HOWEVER PER THE ENGINEER MR. LON CARTER
 AND PER PLANS THERE ARE NO EMERGENCY/ 700 SYSTEMS ON
 THE BACK UP GENERATOR. THIS NEEDS TO BE VERIFIED AS
 THIS WILL AFFECT THE SYSTEMS AS SHOWN.
 NEC 700.9 REQUIRES SYSTEMS TO BE SEPARATED.
 IF THERE ARE ANY ITEMS SUCH AS EMERGENCY LIGHTING ON
 THE LEGALLY REQUIRED TRANSFER SWITCH THIS MAKES THIS A
 700 SYSTEM. ADJUSTMENTS MAY BE NEEDED AT A LATER DATE.
 BASED ON PLANS, THERE ARE ONLY 701 AND 702 SYSTEMS ON
 THE GENERATOR. IT IS IMPORTANT THESE ITEMS BE VERIFIED
 FOR CODE COMPLIANCE.
  