2009-02-12 17:06:06 | ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE PREVIOUS NOTES. NOT ALL INFORMATION |
| ON WHAT PANELS ARE BEING FED FROM THE 700, 701 AND 702 |
| SYSTEMS. |
| THE EMDP AND ATS IS NOW LABELED AS LEGALLY REQUIRED |
| HOWEVER BASED ON THE STAIRWELL LIGHTING ALONE THESE ARE |
| 700 LOADS WHICH ARE EMERGENCY/LIFE SAFETY LOADS. |
| PLEASE SEE 700.9 AS 700 SYSTEMS ARE NOT PERMITTED TO BE |
| WITH 701 SYSTEMS. |
| PLEASE PROVIDE WHAT IS ON ALL PANELS FED FROM ATS-LS. |
| TYPICALLY THE LS DESIGNATION IS FOR LIFE SAFETY NOT |
| LEGALLY REQUIRED. |
| WHAT ARE THE LOADS ON PANELS E-1, E-2 AND E-3. |
| PLEASE ALSO SEE THE PANEL SCHEDULES FOR D1B AND D1A. |
| WHERE ARE THE PANEL SCHEDULES? WHAT LOADS DO THESE |
| PANELS FEED? |
| |
| |
| ** THIS BEING A HIGH RISE BUILDING WHERE ARE THE |
| SYSTEMS SUCH AS EXHAUST FANS, STAIR PRESSURIZATION ETC |
| FED FROM? |
| |
| 408.4, FBC 106.1.1, 106.1.2, 106.3.5.1.2 FOR CLARITY, |
| COORDINATION AND ADDITIONAL INFORMATION NEEDED. |
| |
| *** THERE IS STILL NOT COMPLETE INFORMATION FOR REVIEW. |
| THERE MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |