Plan Review Notes For Permit 08040391 |
Permit Number |
08040391 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-12-26 10:12:40 | ** DENIED** | | | | 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW. THE | | RISER IS NOT COMPLETE WITH ALL DEFINED LOADS, LOAD | | SHEDDING, DESIGNATION OF LEGALLY REQUIRED OR OPTIONAL | | STAND-BY SYSTEMS. | | BASED ON THE ITEMS LISTED ON PANEL HEQ ALL OF THESE | | APPEAR TO BE OPTIONAL STAND-BY LOADS. | | WHAT DOES PANEL D-2 FEED? | | WHAT ABOUT LOADS ON T8 TRANSFORMER, ARE THESE LEGALLY | | REQUIRED OR OPTIONAL STAND-BY? | | THE NEXTEL MAY OR MAY NOT BE LEGALLY REQUIRED DEPENDING | | ON THE TIME IN WHICH IT WAS INSTALLED. | | | | PLEASE SEE DIAGRAM IN 700.9B OF THE 2005 NEC HANDBOOK. | | | | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|