Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop E
Sequence Number 3
Notes
Date Text
2008-12-26 10:12:40** DENIED**
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS REVIEW. THE
 RISER IS NOT COMPLETE WITH ALL DEFINED LOADS, LOAD
 SHEDDING, DESIGNATION OF LEGALLY REQUIRED OR OPTIONAL
 STAND-BY SYSTEMS.
 BASED ON THE ITEMS LISTED ON PANEL HEQ ALL OF THESE
 APPEAR TO BE OPTIONAL STAND-BY LOADS.
 WHAT DOES PANEL D-2 FEED?
 WHAT ABOUT LOADS ON T8 TRANSFORMER, ARE THESE LEGALLY
 REQUIRED OR OPTIONAL STAND-BY?
 THE NEXTEL MAY OR MAY NOT BE LEGALLY REQUIRED DEPENDING
 ON THE TIME IN WHICH IT WAS INSTALLED.
  
 PLEASE SEE DIAGRAM IN 700.9B OF THE 2005 NEC HANDBOOK.
  
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  