Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop B
Sequence Number 3
Notes
Date Text
2008-12-24 09:58:46BUILDING PLAN REVIEW
 PERMIT: 08040391
 ADD: 1001 OKEECHOBEE BLVD
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 DEC.24/2008
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) THE COMPUTATIONS SUBMITTED PAGE 28 FROM SSMA ARE A
 GENERIC TABLE THEY DO NOT REFLECT THE VALUES OF THE
 SCREW TYPE OF ALLOY, GRADE OF MATERIAL SHOULD BE
 VERIFIED BY THE MANUFACTURER. I'VE SPOKEN WITH FORD
 FASTENERS ABOUT THE 1000 STEEL SELF DRILLING SCREW, NO
 VALUES WOULD BE GIVEN BECAUSE THERE HAS BEEN NO TESTING
 FOR THIS FASTENERS. THE SECOND ISSUE IS THE ALTIMATE
 FAILURE STRENGTH VERSES THE DESIGN LOADS OF THE
 FASTENERS BEING USED.
  
 IN THE TABLE SUBMITTEDON PAGE 28 THE THE LINE FOR 43
 MILS IS CIRCLED TOR THICKNESS OF MATERIAL VERES A # 10
 SCREW. SCREW TABLE NOTES ,WHEN CONNECTING MATERIALS OF
 DIFFERENT STEEL THICKNESS OR TENSILE STRENGTH (FU) THE
 LOWEST APPLICABLE VALUES SHOULD BE USED. THE TENSILE
 STRENGTH INDICATED FY+33KSI SHOUD BE USED NOT THE
 43MIL. THIS REDUCES THE PULLOUT TO 66 AND SHEER TO 140.
  
 THE NEST ISSUE IS THE PULL OUT VALUE IS LISTED AS 109
 FOR A #10 SCREW THE SAFETY FACTOR AND THE SAME WITH
 SHEAR VALUES. THE DESIGNER IS TAKING THE ULTIMATE
 FAILURE PRESSURES BY MULTIPLYING THEMBY THREE
 AND THEN CUTTING THE PRESSRES IN HALF THEN MULTIPLYING
 THEM AGAIN BY 1.33 THERE IS NO SAFETY FACORS BUILT INTO
 THE EQUATION.THE THIRD ISSUE IS 33% INCREASE IS TAKEN
 FOR THE FASTENERS. 1605.3.1.1. PLEASE REVIEW SIMILAR
 PROJECT 08070134 WHERE THE SAME VALUES WERE TAKEN.
 1604.1 GENERAL.
 BUILDING, STRUCTURES AND PARTS THEREOF SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH STRENGTH
 DESIGN, LOAD AND RESISTANCE FACTOR DESIGN, ALLOWABLE
 STRESS DESIGN, EMPIRICAL DESIGN OR CONVENTIONAL
 CONSTRUCTION METHODS, AS PERMITTED BY THE APPLICABLE
 MATERIAL CHAPTERS.
  
 THE DESIGN LOADS ON THE PANELS ARE ACTING THE SAME WAY
 AS SHEAR WALLS ACT, SO THE ALLOWABLE STRESS DESIGN.
 2211.2.1 DESIGN SHEAR DETERMINATION.
 WHERE ALLOWABLE STRESS DESIGN (ASD) IS USED, THE
 ALLOWABLE SHEAR VALUE SHALL BE DETERMINED BY DIVIDING
 THE NOMINAL SHEAR VALUE, SHOWN IN TABLES 2211.2(1) AND
 2211.2(2) BY A FACTOR OF SAFETY (OMEGA) WHICH SHALL BE
 TAKEN AS 2.50. ALSO SEE FOOTNOTEA TABLE 2211.2.1. FOR
 SAFETY FACTORS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  