2008-10-25 15:47:02REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING DEFICIENCIES REMAIN AND SHALL BE
 ADDRESSED PRIOR TO PERMIT ISSUANCE:
  
 1. ADDRESS BUILDING PLAN REVIEW COMMENTS RELATED TO
 WIND LOAD ANALYSIS FOR OARTU-1.
  
 2. NO LETTER WAS INCLUDED WITH THIS SUBMISSION FROM
 TRANE REGARDING THEIR ACCEPTANCE OF THE PROPOSED
 REDUCED CLEARANCES FOR SERVICE AND REPLACEMENT OF
 COOLING COILS. ONCE SAID LETTER (TWO COPIES) IS
 PROVIDED, A PROVISO WILL BE ISSUED REQUIRING FIELD
 VERIFICATION BY MECHANICAL INSPECTOR THAT SUFFICIENT
 SPACE EXISTS FOR PROPER SERVICE.
  