2008-10-28 08:13:06 | |
| ** DENIED 2ND REVIEW** |
| |
| |
| 1) NOTE: NEW NOTE WHICH WAS NOT PART OF THE PREVIOUS |
| REVIEW. |
| PLEASE SEE NEC 700.9B THE AHU MAY NOT BE FED FROM THE |
| LIFE SAFETY PANEL OR EQUIPMENT. PLEASE KNOW THIS LOAD |
| IS NOT A LIFE SAFETY OR LEGALLY REQUIRED LOAD. PLEASE |
| ADJUST RISER TO INCLUDE EQUIPMENT TO CREATE AN |
| *OPTIONAL STAND-BY* SYSTEM WHICH STILL MAY BE FED FROM |
| THE SAME GENERATOR IF THE LOAD AND SIZE OF GENERATOR |
| PERMITS WITHOUT LOAD SHEDDING. |
| THIS COMMENT WILL SUBSTANTIALLY CHANGE THE CIRCUITING, |
| RISER ETC. |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |