Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-28 08:13:06 
 ** DENIED 2ND REVIEW**
  
  
 1) NOTE: NEW NOTE WHICH WAS NOT PART OF THE PREVIOUS
 REVIEW.
 PLEASE SEE NEC 700.9B THE AHU MAY NOT BE FED FROM THE
 LIFE SAFETY PANEL OR EQUIPMENT. PLEASE KNOW THIS LOAD
 IS NOT A LIFE SAFETY OR LEGALLY REQUIRED LOAD. PLEASE
 ADJUST RISER TO INCLUDE EQUIPMENT TO CREATE AN
 *OPTIONAL STAND-BY* SYSTEM WHICH STILL MAY BE FED FROM
 THE SAME GENERATOR IF THE LOAD AND SIZE OF GENERATOR
 PERMITS WITHOUT LOAD SHEDDING.
 THIS COMMENT WILL SUBSTANTIALLY CHANGE THE CIRCUITING,
 RISER ETC.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  