Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-01 09:05:36REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE COMMENTS ARE NOT NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS UNDER PERMIT #07030368
  
 1. PAGE S-1 SHOWS THE RTU BEING WELDED TO THE ROOF
 CURB. THIS APPLIANCE SHALL BE ABLE TO BE REPLACED
 WITHOUT REMOVING ELEMENTS OF PERMANENT CONSTRUCTION IN
 ACCORDANCE WITH FBCM 306.1. WELDING THIS APPLIANCE IN
 PLACE WOULD CONSTITUTE PERMANENT CONSTRUCTION. SHOW HOW
 THIS APPLIANCE IS TO BE ATTACHED TO THE BUILDING
 STRUCTURE IN A WAY WHICH STILL ALLOWS FOR SERVICE AND
 REPLACEMENT WHILE MEETING WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBCM 301.13.
  
 2. PAGE S-2 SHOWS WIND LOAD DESIGN FOR THE BUILDING AND
 ATTACHMENTS OF CURB AND RTU TO THE STRUCTURE BUT NO
 INFORMATION WAS PROVIDED REGARDING DESIGN OF THE RTU TO
 WITHSTAND ANTICIPATED WIND PRESSURES. APPLIANCES
 EXPOSED TO WIND SHALL BE DESIGNED TO RESIST ANTICIPATED
 WIND LOADS IN ACCORDANCE WITH FBCM 301.13. PLEASE
 NOTICE THAT THIS APPLIES TO THE APPLIANCE ITSELF AND
 NOT JUST ATTACHMENTS TO THE STRUCTURE. PLEASE PROVIDE
 DOCUMENTATION SHOWING THIS APPLIANCE IS DESIGNED TO
 WITHSTAND WIND PRESSURES IN ACCORDANCE WITH FBCB
 1609.1.
  
 3. PAGE M.4.1: GENERAL NOTE #5 ON THIS PAGE APPEARS TO
 BE IN CONFLICT WITH GENERAL NOTE #3 ON PAGES M.1.1 AND
 M.1.2. PLEASE COORDINATE NOTES AND PAGES. ALSO, NO
 INFORMATION COULD BE FOUND ON STRUCTURAL PLANS
 REGARDING NEW 92X52 ROOF ACCESS OPENING. PROVIDE
 STRUCTURAL DETAIL WITH ALL RELEVANT WIND RESISTANCE
 DOCUMENTATION FOR BUILDING PLAN REVIEW.
  
 4. PAGE M6.1: THE ROOF CURB DETAIL IS IN CONFLICT WITH
 STRUCTURAL DETAILS. PLEASE SEE COMMENT #1 ABOVE AND
 COORDINATE WITH FUTURE STRUCTURAL DETAIL.
  
 5. PREVIOUS PLAN REVIEW COMMENT(S) #3 UNDER PERMIT
 #07030368 HAS NOT BEEN ADDRESSED.
  
 FIRST REVIEW: M4.1 PLEASE SEE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR MINIMUM REQUIREMENTS FOR
 SERVICE ACCESS PER FBC.M 304.1,304.2. EXAMPLE: AHU 3,
 AHU 12 BOTH REQUIRE MIN. 71" ON COIL CONNECTION SIDE OF
 UNIT AND 24" MIN. ON OPPOSITE SIDE. PLAN SHOWS APPROX.
 48" ON COIL SIDE AND 12" ON OPPOSITE SIDE FOR AHU 12.
 THIS UNIT, ONCE IN PLACE, WOULD NOT BE SERVICEABLE.
 MINIMUM SERVICE CLEARANCE FROM ELEMENTS OF PERMANENT
 CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT, IS
 REQUIRED PER FBC,M 306.1.
  
 SECOND REVIEW: REGARDING LETTER FROM TRANE; THIS LETTER
 IS ACCEPTABLE. HOWEVER, PRIOR TO PERMIT ISSUANCE, TWO
 COPIES OF THIS LETTER WITH ORIGINAL SIGNATURE AND SEAL
 OF THE TRANE ENGINEER IS REQUIRED. ALSO, APPROVAL OF
 THE CLEARANCES WILL BE CONDITIONAL PENDING SATISFACTORY
 DEMONSTRATION TO THE FIELD INSPECTOR THAT THE COILS ARE
 IN FACT ABLE TO BE REPLACED AND THE EQUIPMENT IS IN
 FACT ABLE TO BE FULLY SERVICED UNDER ACTUAL FIELD
 CONDITIONS. THIS WILL BE A PROVISO IF AND WHEN PERMIT
 IS APPLIED FOR AND ISSUED.
  
 ***NO LETTER FROM TRANE WAS FOUND IN THIS SUBMITTAL
 PACKAGE. PROVIDE TWO COPIES AS REQUESTED IN PREVIOUS
 REVIEW. THIS WILL FACILITATE PERMIT ISSUANCE WITH
 PROVISO PENDING FIELD VERIFICATION OF SERVICEABILITY OF
 AIR HANDLERS AS INSTALLED. FBCM 306.1.
  
 6. PLEASE CORRECT THE ADDRESS ON MECHANICAL AND
 ELECTRICAL PAGES TO CORRESPOND WITH THE ADDRESS ON THE
 PERMIT APPLICATION.
  