Plan Review Notes
Plan Review Notes For Permit 08040391
Permit Number 08040391
Review Stop G
Sequence Number 1
Notes
Date Text
2008-04-18 16:38:20GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 NOTE: SHEET M0.2, M.2.3, AND P2.1 ARE INDICATING 1"
 NATURAL GAS TO THE OARTU-1 CHILLED WATER UNIT.
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS
 SECTION 401.1 SCOPE.
  
 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 ON THE GAS ISOMETRIC. PER FBC FUEL GAS SECTION 401.1
 SCOPE.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM
 IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS
 CONNECTING TO.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM
 IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS
 CONNECTING TO.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: IF NATURAL GAS DELIVERY PRESSURE IS 2 PSI OR
 MORE PLEASE PROVIDE TWO COPIES OF THE MP REGULATOR
 MANUFACTURER'S SPECIFICATIONS THAT CLEARLY INDICATE THE
 MAKE MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 *NOTE: PROVIDE TWO COPIES OF MANUFACTURER'S
 SPECIFICATION SHEETS OF THE NEW CHILLED WATER OARTU-1
 UNIT THAT CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU
 CAPCITY, AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved