Date |
Text |
2008-04-18 16:38:20 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| NOTE: SHEET M0.2, M.2.3, AND P2.1 ARE INDICATING 1" |
| NATURAL GAS TO THE OARTU-1 CHILLED WATER UNIT. |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. PER FBC FUEL GAS |
| SECTION 401.1 SCOPE. |
| |
| 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| ON THE GAS ISOMETRIC. PER FBC FUEL GAS SECTION 401.1 |
| SCOPE. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM |
| IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS |
| CONNECTING TO. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| *NOTE: THIS INCLUDES THE EXISTING NATURAL GAS SYSTEM |
| IN THE KITCHEN THAT THE NEW PROPOSED OARTU-1 UNIT IS |
| CONNECTING TO. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| NOTE: IF NATURAL GAS DELIVERY PRESSURE IS 2 PSI OR |
| MORE PLEASE PROVIDE TWO COPIES OF THE MP REGULATOR |
| MANUFACTURER'S SPECIFICATIONS THAT CLEARLY INDICATE THE |
| MAKE MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING |
| FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| *NOTE: PROVIDE TWO COPIES OF MANUFACTURER'S |
| SPECIFICATION SHEETS OF THE NEW CHILLED WATER OARTU-1 |
| UNIT THAT CLEARLY INDICATE THE MAKE, MODEL NUMBER, BTU |
| CAPCITY, AND A LISTING FROM A NATIONALLY RECOGNIZED |
| TESTING LABORATORY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |