1 |
|
Notes |
Date |
Text |
2008-04-16 18:58:42 | RESIDENTIAL (R3) SHUTTERSINSTALLATION, BUILDING | | REVIEW CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1-REVISE SHUTTER SPAN SHOWNON COLUMN #6 OF | | INSTALLATION SCHEDULE.SIZE SHOWN IS THE SAME SIZE AS | | THE OPENING SIZE.THIS DOESN'T WORK IF THE EDGE | | DISTANCE (TOP AND BOTTOM) IS 3.5" AS SHOWN ON | | INSTALLATION SCHEDULE COLUMN#8. REVISE AS REQUIRED. | | | | 2-ANCHOR SPECIFIED ON COLUMN #10 OF INSTALLATION | | SCHEDULE IS A1/4 - 1 1/4 ELCO/BUILDEX HEX HEAD MAXI | | SET TAPCON.SEE PAGE 14 OF 26 OF STORM SHUTTERSFOR | | SPECIFIC TYPE OF TAPCON TO BE USED AND SPECIFIC MINIMUM | | EMBEDMENT REQUIRED FOR CONCRETE AND FOR CONCRETE BLOCK. | | REVISE AS REQUIRED. | | | | 3- CLARIFY WHAT DOES PC/CB ON COLUMN #11 OF | | INSTALLATION SCHEDULE STANDS FOR. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|