2008-04-17 13:23:29 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET M/P-1 SANITARY RISER PLEASE CORRECT THE |
| FOLLOWING ITEMS. |
| |
| A} THE WASHING MACHINE DOES NOT REFLECT THE FLOOR PLAN |
| ON THE SANITARY RISER. THE SANITARY RISER IS INDICATING |
| THE WASHER IN THE EXISTING SCREEN PORCH. PLEASE CORRECT |
| THIS PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS AND FBC PLUMBING |
| SECTION 701.1 SCOPE. |
| |
| B} THE WASHING MACHINE STACK REQUIRES A 3" CLEANOUT TO |
| BE LOCATED AT 4' A.F.F. PER FBC PLUMBING SECTION 708.7 |
| MINIMUM SIZE AND SECTION 708.9 ACCESS. |
| |
| C} THE LAVATORY REQUIRES A WATER SEAL TRAP. PER FBC |
| PLUMBING SECTION 1002.1 FIXTURE TRAPS. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |