2008-04-16 12:16:19PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.3
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 3) SHOW THE SIZE OF THE SUPPLY AIR TRUNK LINE, SEE
 YELLOW HIGH LIGHT ON PAGE M/P-1, PER 2004 WPB AMEND.
 106.3.5.4 (10).
  
 4) SHOW ON MECHANICAL PLAN WHERE THE CLOTHES DRYER VENT
 WILL DISCHARGE TO, SEE 2004 FBC/R R303.4.2.
  
 5) SHOW THE SEER AND TOTAL COOLING BTU'S FOR THE A/C
 SYSTEM ON THE MECHANICAL PLAN, SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 6)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE PAGE M/P-1 COULD NOT BE FOUND ON THE
 ARI DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]