Plan Review Notes
Plan Review Notes For Permit 08040313
Permit Number 08040313
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-15 11:34:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE
 PLAN IS NEW OR EXISTING. IF NEW INCLUDE IN THE
 DESCRIPTION ON THE APPLICATION, PROVIDE AN AIC RATING
 PER 110.9 AND 110.10.
  
 2} CIRCUIT #7 BATH LIGHT AND RECEPTACLE HAS AN OCP OF
 30 AMPS WITH A #12 CONDUCTOR IN VIOLATION OF 310.16.
 THIS CIRCUIT IS REQUIRED TO BE 20 AMP PER
 210.11(C)(3).
  
 3} THERE IS A HOT TUB ON THE PANEL SCHEDULE THAT IS NOT
 LOCATED ON THE PLAN. SHEET A-1 INDICATES A SHOWER IN
 THE BATHROOM. SEE 680.43(A)(2) FOR GFCI REQUIREMENTS.
  
 4} THE "MAIN HOUSE SUB PANEL" IS LISTED AT 100 AMPS IN
 PANEL "A", BUT SHOWN AS 110 AMPS ON THE RISER
  
 5} THERE IS NO REFRIGERATOR LISTED IN THE LOAD
 CALCULATIONS, YET ONE IS LISTED IN THE PANEL SCHEDULE
 AND SHOWN ON THE PLAN CONFIRM THAT THERE IS NO OTHER
 APPLIANCES THAT ARE REQUIRED TO BE IN THE LOAD
 CALCULATIONS. CONFIRM THE WATER HEATER IS IN THE MAIN
 HOUSE AND THERE IS NONE IN THE ACCESSORY BUILDING.
  
 6} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14,RECEPTACLE PER 210.63, FOR THE A/C.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718