| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS |
| AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE |
| FOLLOWING: |
| |
| 1}INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE |
| PLAN IS NEW OR EXISTING. IF NEW INCLUDE IN THE |
| DESCRIPTION ON THE APPLICATION, PROVIDE AN AIC RATING |
| PER 110.9 AND 110.10. |
| |
| 2} CIRCUIT #7 BATH LIGHT AND RECEPTACLE HAS AN OCP OF |
| 30 AMPS WITH A #12 CONDUCTOR IN VIOLATION OF 310.16. |
| THIS CIRCUIT IS REQUIRED TO BE 20 AMP PER |
| 210.11(C)(3). |
| |
| 3} THERE IS A HOT TUB ON THE PANEL SCHEDULE THAT IS NOT |
| LOCATED ON THE PLAN. SHEET A-1 INDICATES A SHOWER IN |
| THE BATHROOM. SEE 680.43(A)(2) FOR GFCI REQUIREMENTS. |
| |
| 4} THE "MAIN HOUSE SUB PANEL" IS LISTED AT 100 AMPS IN |
| PANEL "A", BUT SHOWN AS 110 AMPS ON THE RISER |
| |
| 5} THERE IS NO REFRIGERATOR LISTED IN THE LOAD |
| CALCULATIONS, YET ONE IS LISTED IN THE PANEL SCHEDULE |
| AND SHOWN ON THE PLAN CONFIRM THAT THERE IS NO OTHER |
| APPLIANCES THAT ARE REQUIRED TO BE IN THE LOAD |
| CALCULATIONS. CONFIRM THE WATER HEATER IS IN THE MAIN |
| HOUSE AND THERE IS NONE IN THE ACCESSORY BUILDING. |
| |
| 6} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| 440.14,RECEPTACLE PER 210.63, FOR THE A/C. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |