2008-04-22 08:44:43 | 2004 FBC W/2007 REVISIONS |
| CHANGE OF OCCUPANCY |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. PHONE (561) |
| 233-5025 |
| |
| 3) THE DECLARED VALUE OF THE WORK IS TOO LOW. THE VALUE |
| IS REQUIRED TO REFLECT THE COSTS OF LABOR, MATERIALS, |
| OVERHEAD AND PROFIT THAT WOULD BE REQUIRED TO CONVERT |
| THE GARAGE TO AN OFFICE. INCLUDING ALL OF THE |
| UN-PERMITTED WORK. PLEASE REVISE. FBC 108.3* CITY |
| AMENDMENTS. |
| |
| 4) SUBMIT TWO COPIES OF ENERGY CALCULATION FORMS AS |
| REQUIRED BY FBC 13-600. THE OWNER/AGENT IS REQUIRED TO |
| SIGN THE FORMS. |
| |
| 5) SPECIFY THE INSULATION R-VALUES FOR THE WALL AND |
| CEILING INSULATION. SEE FBC 13-600. |
| |
| 6) THE CONSTRUCTION TYPE SPECIFIED ON SHEET SP-1 IS |
| INCOMPLETE. SPECIFY CONSTRUCTION TYPE VA FOR ONE HOUR |
| PROTECTED OR TYPE VB FOR UNPROTECTED. SEE FBC TABLE |
| 601. |
| |
| 7) THE DOOR TO BATHROOM IS REQUIRED TO HAVE A 29" CLEAR |
| OPENING PER FBC EXISTING BUILDING SECTION 812.5 AND FBC |
| 11-4.22.2. |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR EACH TYPE |
| OF EXTERIOR DOOR AND STORM PANELS. SPECIFY THE MOUNT |
| TYPE, FASTENER TYPE AND SPACING, EDGE DISTANCE, SPANS, |
| ETC. FOR THE STORM PANELS. |
| |
| 9) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 10) THE CLASSIFICATION OF WORK ON SHEET SP-1 IS |
| INCORRECT. THIS IS CONSIDERED A CHANGE OF OCCUPANCY NOT |
| A LEVEL 2 ALTERATION. SEE 2004 FBC EXISTING BUILDING |
| CHAPTER 3. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |