2008-04-19 10:48:36BUILDING PLAN REVIEW
 PERMIT: 08040311
 ADD: 1307 N. MANGONIA DR
 CONT: SOUTHERN HOMES EXTERIORS
 TEL: (561)533-9100
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 FBC FLORIDA BUILDING CODE 2004 WITH 2007 REVISIONS
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 XX1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH THE
 CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 XX2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT. SEE INSTALLATION SCHEDULE IN PACKAGE.
  
 XX6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS APPLY
 TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 NOTE: THE EDGE DISTANCE ON SHEET 11 SHALL BE INDICATED
 ON THE INSTALLATION SCHEDULE AND ON THE PRODUCT
 APPROVAL. SHEET #10 IS INCOMPLETE, THE INFORMATION
 REGARDING ANCHOR SPACING WALL MOUNT #1 AND #3 IS NOT
 INDICATED. IF THE EDGE DISTANCE IS 3 INCHES OR LESS THE
 FACTORS FROM THE EDGE DISTANCE TABLE SHALL BE TAKEN
 INTO CONSIDERATION FOR THE ANCHOR SPACING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]