2008-08-01 16:35:41PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, CORRECTIONS TO THE ENERGY CODE
 COMPLIANCE FORM ARE REQUIRED BEFORE REVIEW STATUS WILL
 BE PASSED:
  
 1. THE ADDRESS LISTED ON THE COVER PAGE OF THE
 COMPLIANCE FORM IS LISTED AS 1641 WORTHINGTON RD. THIS
 IS NOT THE ADDRESS FOR THIS PROJECT. PLEASE CORRECT.
  
 2. THE SYSTEM SIZING SUMMARY SHALL BE SIGNED AND SEALED
 IN ADDITION TO THE ENERGY CALCULATIONS IN ACCORDANCE
 WITH FBCB 13-407.1.ABC.1(2).
  
 IF THESE ITEMS CAN BE CORRECTED DURING THIS REVIEW
 CYCLE, THE REVIEW STATUS WILL BE CHANGED TO PASS.
  