Plan Review Notes
Plan Review Notes For Permit 08040298
Permit Number 08040298
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-08-07 11:49:26*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.NO
 ADDRESS SHOWN ON SHEETS PD-1 THRU PD-5
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO AN APPROPIATE PLAN SHEET
  
 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 THE VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .ADD TO AN APPROPIATE PLAN SHEET
  
 7.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A-2),
 DISPLAY/SHOW THE NUMERICAL ADDRESS ON THE STRUCTURE OF
 THE BUIDING WHICH FRONTS THE PROPERTY.AS PER WEST
 PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.ADD TO
 ADDRESS VERBAGE ON SHEET A-2 (CAPTION 1 - WEST
 ELEVATION) THAT THE WIDTH/STROKE OF ADDRESS NUMBERS
 SHALL BE NO LESS THAN 1" .
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722