2008-08-05 09:37:42 | BUILDING PLAN REVIEW |
| PERMIT: 08040298 |
| ADD: 406 COLUMBIA DRIVE |
| CONT: WEST CONSTRUCTION |
| TEL: (561)588-2027 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 2-5) COMPLIED. |
| |
| 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| 6A) COMPLIED |
| 6B) COMPLIED |
| 6C) COMPLIED |
| 6D) EXTERIOR LOUVERS/ VENT 3"X10" OK NOT TO NEED |
| PRODUCT APPROVAL/ SIMILAR AS GLASS BLOCK WILL NOT |
| PRESSURIZE WHOLE BUILDING IF DAMAGED. |
| 6E) ROOFING ASSEMBLIES/ROOF TILE- INDICATE TYPE OF |
| FASTENING SYSTEM |
| |
| 7)USING NOA'S OK COMPLIED |
| |
| 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 9)PLEASE PROVIDE ENERGY COMPLIANCE FORMS FOR NEW |
| CONSTRUCTION SEE 13.400.0 ABC . |
| 9A) PLEASE PROVIDE THE CORRECT ADDRESS ON THE PROJECT |
| SUMMARY SHEET. |
| 9B) THE INPUT DATA REPORTSHEET 2& 3 FOR WALLS |
| INDICATES THE USE OF 8 INCH BLOCK WITH 3/4" ISO |
| INSULATION SWERE AS SHEET A-2 DETAILS 5 & 6 SHOW STUCCO |
| DIRECTLY APPLIED TO THE INTERIOR WALLS. |
| 9C) EXTERIOR DOORS 1 & 3 BOTH SHOW AS A INSULATED DOOR |
| SYSTEM BUT THE PRODUCT APPROVALS SUBMITTED ARE NOT. |
| 9D) ROOF INSULATION THE COMPLIANCE FORM INDICATES THE |
| USE OF 6 INCH BATTS WHERE AS THE PLANS CALL FOR FOAN |
| ISONENE INSULATION, PLEASE PROVIDE MANUFACTURERS |
| INFORMATION AS TO THE THICKNESS AND R-VALUES |
| FOR THIS TYPE INSULATION. |
| 9E) IN THE INPUT DATA REPORT SHEET # 4 FOR FLOORS YOU |
| HAVE TAKEN INSULATION VALUES FOR CARPET AND RUBBER PAD, |
| PLEASE CORRELATE PLANS AND ENERGY CALCS. |
| 9F) PLEASE SEE SHEET # 5 FOR FENESTRATION, THE INPUT |
| REPORT IS BLANK FOR GLAZED OPENINGS WHERE ASSHEET A-2 |
| DETAIL 4 INDICATES 27 SQ FT OF GLAZED OPENING, AGAIN |
| PLEASE CORRELATE. |
| |
| 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |