Plan Review Notes
Plan Review Notes For Permit 08040298
Permit Number 08040298
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-17 15:40:34DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
  
 1. PLANS SHALL BE DESIGNED TO FBC-2004 W/2007
 AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION 106.1.3.
  
 2. THE CORRECT ADDRESS, (406 COLUMBIA DR), SHALL BE
 INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 3. SHT D-1 INDICATES THE DEMOLITION/REMOVAL OF AN
 EXISTING 1 STORY BUILDING. THIS IS NOT INDICATED ON THE
 PERMIT APPLICATION WHICH STATES, "DESCRIBE PROJECT IN
 DETAIL". PLEASE INDICATE ALL MAJOR WORK FOR PROJECT ON
 THE APPLICATION. SECTION 105.1.
  
 4. SHT A-1 PER TABLES 1004.1.2 & 403.1, ONE TOILET, ONE
 LAV, ONE SERVICE SINK AND ONE DRINKING FOUNTAIN ARE
 REQUIRED. ALSO SEE SECTION 411 AS ONE EMERGENCY EYE
 WASH OR EMERGENCY SHOWER MAY BE REQUIRED. PLEASE
 INDICATE THE LOCATION OF ALL FIXTURES REQUIRED. ALSO
 INDICATE THE TYPE AND AMOUNT OF MATERIALS BEING STORED
 AS WELL AS THE MSDS SHEETS FOR THE MATERIALS. SECTION
 411.
  
 5. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]