Date |
Text |
2008-04-17 15:40:34 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| |
| 1. PLANS SHALL BE DESIGNED TO FBC-2004 W/2007 |
| AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION 106.1.3. |
| |
| 2. THE CORRECT ADDRESS, (406 COLUMBIA DR), SHALL BE |
| INDICATED ON THE TITLE BLOCK OF EACH SHEET. SECTION |
| 106.1.1. |
| |
| 3. SHT D-1 INDICATES THE DEMOLITION/REMOVAL OF AN |
| EXISTING 1 STORY BUILDING. THIS IS NOT INDICATED ON THE |
| PERMIT APPLICATION WHICH STATES, "DESCRIBE PROJECT IN |
| DETAIL". PLEASE INDICATE ALL MAJOR WORK FOR PROJECT ON |
| THE APPLICATION. SECTION 105.1. |
| |
| 4. SHT A-1 PER TABLES 1004.1.2 & 403.1, ONE TOILET, ONE |
| LAV, ONE SERVICE SINK AND ONE DRINKING FOUNTAIN ARE |
| REQUIRED. ALSO SEE SECTION 411 AS ONE EMERGENCY EYE |
| WASH OR EMERGENCY SHOWER MAY BE REQUIRED. PLEASE |
| INDICATE THE LOCATION OF ALL FIXTURES REQUIRED. ALSO |
| INDICATE THE TYPE AND AMOUNT OF MATERIALS BEING STORED |
| AS WELL AS THE MSDS SHEETS FOR THE MATERIALS. SECTION |
| 411. |
| |
| 5. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| THE BUILDING. SECTION 608.13.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |