Plan Review Notes For Permit 08040298
Permit Number 08040298
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-05-15 10:46:55*****DENIED*****
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS RESPONSE TO THE SAID PROPERTY OR
 THE VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES) .
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.THE FIRE EXTINGUISHER(S) SHALL BE 2A10BC FIRE RATED
 WITHIN A 75' TRAVEL DISTANCE MOUNTED/INSTALLED IN AN
 OBVIOUS AND ACCESSIBLE LOCATION.
  
 7.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A-2),
 DISPLAY/SHOW THE NUMERICAL ADDRESS ON THE STRUCTURE OF
 THE BUIDING WHICH FRONTS THE PROPERTY.AS PER WEST
 PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722