Plan Review Notes
Plan Review Notes For Permit 08040298
Permit Number 08040298
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-14 19:03:58** DENIEDREVIEW**
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE
 STATED ON PLANS. (ELECTRICAL SHEETS AT A MINIMUM).
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS AS
 REQUIRED PER FBC CHAPTER 13 WERE SUBMITTED.
 PLEASE BE SURE TO SEE 13-400.3.A, 13-400.3.B,
 13-400.3.C, 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2
 ETC
 PLEASE SEE COMPLIANCE WITH THE FBC AND CHAPTER 13 CAN
 NOT BE VERIFIED AT THIS TIME.
 PLEASE ALSO SEE COMMENTS FROM MECHANICAL AND BUILDING
 REVIEWS.
 ** THE LIGHTING PERFORMANCE ADDED TO E4.1 DOES NOT MEET
 THE MINIMUM FOR CODE COMPLIANCE AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE FIXTURES WHICH ARE SHOWN ON
 E0.1 AND E4.1 DO NOT CORRELATE.
 PLEASE SEE NOTE #2 ABOVE AND BE SURE TO ADJUST ALL.
  
 4) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE AS
 RISER SHOWS PANEL AS 100AMP MCB AND THE PANEL SHOWS
 90AMP MLO WHICH CONTAINS NO MAIN AS REQUIRED.
 FBC 106.1.2 FOR COORDINATION AND NEC 230.70, 71, 76, 79
 FOR MAIN.
  
 5) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL PER
 250.50 AND ANY METALLIC COLD WATER PIPE.
 THE GROUNDING DETAIL ON E7.1 IS NOT COMPLETE WITH THESE
 ITEMS.
 PLEASE ALSO SEE THE GROUNDING DETAIL MENTIONS TO SEE
 PANEL FOR THE SIZE OF THE GROUNDING ELECTRODE PER
 250.66 YET THE RISER SHOWS A GROUNDING ELECTRODE
 CONDUCTOR OF A DIFFERENT SIZE??
 PLEASE COORDINATE AND ADJUST PLANS.
  
 6) NOTE: PLEASE SEE OCTAGONAL NOTES ON RISER WHICH ARE
 NOT ON THE KEYED NOTE SCHEDULE.
 FOR EXAMPLE: #4.
  
 7) NOTE: INFORMATION HAS BEEN ROUTED TO THE ADDRESSING
 REVIEWER. ONCE THE FINAL ADDRESS HAS BEEN DETERMINED,
 PLEASE BE SURE TO ADD THE CORRECT ADDRESS TO THE TITLE
 BLOCKS ON EACH SHEET.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.3.5
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]