2008-04-14 19:03:58 | ** DENIEDREVIEW** |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES NEED TO BE |
| STATED ON PLANS. (ELECTRICAL SHEETS AT A MINIMUM). |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SEE THAT NO ENERGY CALCULATIONS AS |
| REQUIRED PER FBC CHAPTER 13 WERE SUBMITTED. |
| PLEASE BE SURE TO SEE 13-400.3.A, 13-400.3.B, |
| 13-400.3.C, 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2 |
| ETC |
| PLEASE SEE COMPLIANCE WITH THE FBC AND CHAPTER 13 CAN |
| NOT BE VERIFIED AT THIS TIME. |
| PLEASE ALSO SEE COMMENTS FROM MECHANICAL AND BUILDING |
| REVIEWS. |
| ** THE LIGHTING PERFORMANCE ADDED TO E4.1 DOES NOT MEET |
| THE MINIMUM FOR CODE COMPLIANCE AT THIS TIME. |
| |
| 3) NOTE: PLEASE SEE THE FIXTURES WHICH ARE SHOWN ON |
| E0.1 AND E4.1 DO NOT CORRELATE. |
| PLEASE SEE NOTE #2 ABOVE AND BE SURE TO ADJUST ALL. |
| |
| 4) NOTE: PLEASE CORRELATE RISER AND PANEL SCHEDULE AS |
| RISER SHOWS PANEL AS 100AMP MCB AND THE PANEL SHOWS |
| 90AMP MLO WHICH CONTAINS NO MAIN AS REQUIRED. |
| FBC 106.1.2 FOR COORDINATION AND NEC 230.70, 71, 76, 79 |
| FOR MAIN. |
| |
| 5) NOTE: PLEASE SEE MISSING REQUIRED FOOTER STEEL PER |
| 250.50 AND ANY METALLIC COLD WATER PIPE. |
| THE GROUNDING DETAIL ON E7.1 IS NOT COMPLETE WITH THESE |
| ITEMS. |
| PLEASE ALSO SEE THE GROUNDING DETAIL MENTIONS TO SEE |
| PANEL FOR THE SIZE OF THE GROUNDING ELECTRODE PER |
| 250.66 YET THE RISER SHOWS A GROUNDING ELECTRODE |
| CONDUCTOR OF A DIFFERENT SIZE?? |
| PLEASE COORDINATE AND ADJUST PLANS. |
| |
| 6) NOTE: PLEASE SEE OCTAGONAL NOTES ON RISER WHICH ARE |
| NOT ON THE KEYED NOTE SCHEDULE. |
| FOR EXAMPLE: #4. |
| |
| 7) NOTE: INFORMATION HAS BEEN ROUTED TO THE ADDRESSING |
| REVIEWER. ONCE THE FINAL ADDRESS HAS BEEN DETERMINED, |
| PLEASE BE SURE TO ADD THE CORRECT ADDRESS TO THE TITLE |
| BLOCKS ON EACH SHEET. |
| THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| FAC 61G1-16.004, 61G15-23.002 |
| FBC 106.3.5 |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |