2008-04-23 15:51:18 | BUILDING PLAN REVIEW |
| PERMIT: 08040298 |
| ADD: 406 COLUMBIA DRIVE |
| CONT: SISCA CONSTRUCTION |
| TEL: (561)228-7517 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE2007 SUPPLEMENTS PLEASE UPDATE SHEET |
| A-1. |
| |
| 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 3)COMPLIED, UNITY OF TITLE. |
| |
| 4)PLANS INDICATE (SHEET A-1) THERE TO BE A PLYWOOD |
| DECK IN THE ROOF TRUSSES FOR STORAGE. TABLE 1607.1 ONLY |
| PROVIDES LIVE LOADS FOR ATTIC STORAGE IN RESIDENCES. |
| 1607.11 DOES INDICATE THE STRUCTURAL SUPPORTS SHALL BE |
| DESIGNED FOR DEAD LOADS AS WELL AS FOR LIVE LOADS. |
| PLEASE PROVIDE WHAT THE MAXIMUM LOADING PER SQ FT WILL |
| BE FOR THESE STORAGE AREAS . |
| |
| 5)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE |
| DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE |
| TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| MISSILE TEST. |
| |
| 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR |
| OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS |
| FOLLOWS: |
| 6A) FIXED WINDOWS |
| 6B) EXTERIOR SWING DOORS |
| 6C) COIL DOORS OR OVERHEAD DOORS |
| 6D) EXTERIOR LOUVERS |
| 6E) ROOFING ASSEMBLIES |
| ROOF TILE |
| |
| 7) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 9)PLEASE PROVIDE ENERGY COMPLIANCE FORMS FOR NEW |
| CONSTRUCTION SEE 13.400.0 ABC . |
| |
| 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |