Plan Review Notes
Plan Review Notes For Permit 08040296
Permit Number 08040296
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-17 14:02:23 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PLANS SUBMITTED INDICATE RELOCATING AN EXISTING
 LIGHT POLE. A ELECTRICAL PERMIT IS REQUIRED FOR THAT
 WORK.
  
 2} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718