Date |
Text |
2008-04-10 07:57:21 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| ____1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE |
| MITIGATION. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| EACH ROOF TYPE |
| |
| _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED FOR THE POLYGLASS TU PLUS, FAC9B72, AND |
| FLORIDA STATE PRODUCT APPROVAL REQUIRED IN ADDITION TO |
| THE NOA PROVIDED FOR THE VANGUARD TILE, |
| WWW.FLORIDABUILDING.ORG.TWO COMPLETE COLLATED SETS OF |
| DOCUMENTS REQUIRED FOR PERMIT ISSUANCE. |
| |
| ____4.)FOR THE FLAT ROOF, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| LIMITATIONS. |
| |
| ____5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| SHEET). |
| |
| ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| |
| ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |