Plan Review Notes For Permit 08040219 |
Permit Number |
08040219 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-19 07:32:30 | | | | | DENIED | | | | 1)THE MOUNTING PER THE PRODUCT APPROVALS REQUIRES THE | | SILL ATTACHMENT AS TYPE "D" TYPE "A" CANNOT BE USED ON | | THE BOTTOM. IN THIS CASE THE O/C SPACING WOULD BE 7" X | | .5 FOR THE 2" EDGE DISTANCE FACTOR ON PAGE 14 = 3 1/2" | | O/C. PLEASE MAKE CORRECTIONS TO THE SHUTTER SCHEDULE | | AND PRODUCT APPROVALS. | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|