Plan Review Notes
Plan Review Notes For Permit 08040196
Permit Number 08040196
Review Stop M
Sequence Number 1
Notes
Date Text
2008-04-14 14:12:34PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) FROM THE PLANS SUBMITTED IT APPEARS YOU WISH TO
 PRODUCE A TENANT SEPARATION WALL, SEE 2004 FBC 708.1.
  
 ***SECTION 708FIRE PARTITIONS
  
 708.1 GENERAL.
 THE FOLLOWING WALL ASSEMBLIES SHALL COMPLY WITH THIS
 SECTION.
 1. WALLS SEPARATING DWELLING UNITS IN THE SAME
 BUILDING.
 2. WALLS SEPARATING SLEEPING UNITS IN OCCUPANCIES
 IN GROUP R-1, HOTEL OCCUPANCIES, R-2 AND I-1.
 3. WALLS SEPARATING TENANT SPACES IN COVERED MALL
 BUILDINGS AS REQUIRED BY SECTION 402.7.2 .
 4. CORRIDOR WALLS AS REQUIRED BY SECTION 1016.1 .
 5.WALL SEPARATING INDIVIDUAL TENANT SPACES.
 (TENANT SEPARATION WALL).
  
 EXCEPTIONS:
 1. IN GROUP B AND S OCCUPANCIES WALLS USED TO
 SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE
 FIRE-RESISTANCE RATING, PROVIDED NO AREA BETWEEN FIRE
 PARTITIONS HAVING A 1-HOUR FIRE-RESISTANCE RATING
 EXCEEDS 3,000 SQUARE FEET (279 M 2 ).
  
 2) PLEASE PROVIDE INFORMATION SHOWING COMPLIANCE WITH
 EXCEPTION 1. IF YOU CAN NOT MEET THE EXCEPTION PLEASE
 RATE THE WALL AND SHOW HOW ALL PENETRATIONS WILL COMPLY
 WITH THE 2004 FBC.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]