Plan Review Notes
Plan Review Notes For Permit 08040195
Permit Number 08040195
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-09 10:55:082004 FBC W/2007 REVISIONS
 INSTALL ACCORDION SHUTTER
  
 DENIED BY BUILDING
  
 1)THE BUILDING HAS A MEAN ROOF HEIGHT OF 210 FEET,
 THE COMPONENT AND CLADDING PRESSURE CALCULATIONS ARE
 REQUIRED TO BE PERFORMED BY A FLORIDA LICENSED ENGINEER
 AND BE SIGNED, SEALED AND DATED.
  
 2) THE CORRECT EDITION OF ASCE7 IS ASCE7-02.
  
 3) SPECIFY IF THE OPENING IS LOCATED IN AN EDGE OR
 INTERIOR WALL ZONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]