Plan Review Notes For Permit 08040195 |
Permit Number |
08040195 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-09 10:55:08 | 2004 FBC W/2007 REVISIONS | | INSTALL ACCORDION SHUTTER | | | | DENIED BY BUILDING | | | | 1)THE BUILDING HAS A MEAN ROOF HEIGHT OF 210 FEET, | | THE COMPONENT AND CLADDING PRESSURE CALCULATIONS ARE | | REQUIRED TO BE PERFORMED BY A FLORIDA LICENSED ENGINEER | | AND BE SIGNED, SEALED AND DATED. | | | | 2) THE CORRECT EDITION OF ASCE7 IS ASCE7-02. | | | | 3) SPECIFY IF THE OPENING IS LOCATED IN AN EDGE OR | | INTERIOR WALL ZONE. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|