Plan Review Notes For Permit 08040194 |
Permit Number |
08040194 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-14 14:19:56 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | FS, RESPECTIVELY. | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | IF EXEMPTIONS APPLY. | | | | 2} AN ELECTRICAL PERMIT IS REQUIRED FOR THE DEMOLITION | | OF WALLS AND CEILINGS IN WHICH ELECTRICAL DEVICES OR | | RACEWAYS PASS THROUGH OR TERMINATE. NO ELECTRICAL | | CONTRACTOR WAS SIGNED ON THE APPLICATION, A SEPARATE | | PERMIT APPLICATION IS REQUIRED.105.2 FBC AS AMENDED. | | | | 3} INDICATE WHAT IS TO BE DEMOLISHED, WHICH WALLS, | | CEILINGS, ETC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|