Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-04-21 12:33:17*****UNSAT*****
  
  
 1.PROVIDE A SPRINKLER LAYOUT OF THE PROPOSED FLOOR
 PLAN.
  
 2.ON SHEET A-3, AMEND SMOKE DETECTORS (SD) TO REFLECT
 SMOKE ALARMS (SA);BE ADVISED THAT SD'S ARE TIED INTO
 THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SA'S ALERT THE
 OCCUPANT(S) OF THE DWELLING UNIT ONLY.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW