Date |
Text |
2008-04-11 09:42:45 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} INDICATE COMPLIANCE WITH THE FOLLOWING: NFPA-72, |
| 11.5.1.2 NOTIFICATION. |
| (A)FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL |
| PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE |
| DWELLING AREAS. |
| (B)WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS |
| INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED |
| SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES |
| THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE |
| DWELLING UNIT TO SOUND. |
| |
| THE SMOKE ALARMS IN THE UNIT MUST BE INTERCONNECTED AND |
| THEREFORE MUST BE FED FROM ONLY ONE CIRCUIT. IF THAT IS |
| THE INTENT WITH USING CIRCUIT #17, IN PLACE OF CIRCUITS |
| #19 AS IN THE PANEL SCHEDULE, THEN DESIGNATE WHICH |
| PANEL FEEDS THAT CIRCUIT. |
| |
| 2} DESIGNATE THE PANELS IN A MANNER THAT ALLOWS CIRCUIT |
| NUMBERS TO BE IDENTIFIED WITH THE PANEL OF ORIGIN. |
| |
| 3} THE DINING ROOM RECEPTACLES ARE ON CIRCUIT #18 IN |
| THE PANEL SCHEDULE, BUT ONE IS NUMBERED 14 ON THE PLAN. |
| CORRELATE ALL CIRCUIT NUMBERS WITH PANEL PER COMMENT |
| #2.EG NO FAMILY ROOM IN THE SCHEDULE. SEE 408.4 CIRCUIT |
| DIRECTORY OR CIRCUIT IDENTIFICATION |
| |