Plan Review Notes
Plan Review Notes For Permit 08040184
Permit Number 08040184
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-11 09:42:45 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INDICATE COMPLIANCE WITH THE FOLLOWING: NFPA-72,
 11.5.1.2 NOTIFICATION.
 (A)FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL
 PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE
 DWELLING AREAS.
 (B)WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS
 INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED
 SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES
 THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE
 DWELLING UNIT TO SOUND.
  
 THE SMOKE ALARMS IN THE UNIT MUST BE INTERCONNECTED AND
 THEREFORE MUST BE FED FROM ONLY ONE CIRCUIT. IF THAT IS
 THE INTENT WITH USING CIRCUIT #17, IN PLACE OF CIRCUITS
 #19 AS IN THE PANEL SCHEDULE, THEN DESIGNATE WHICH
 PANEL FEEDS THAT CIRCUIT.
  
 2} DESIGNATE THE PANELS IN A MANNER THAT ALLOWS CIRCUIT
 NUMBERS TO BE IDENTIFIED WITH THE PANEL OF ORIGIN.
  
 3} THE DINING ROOM RECEPTACLES ARE ON CIRCUIT #18 IN
 THE PANEL SCHEDULE, BUT ONE IS NUMBERED 14 ON THE PLAN.
 CORRELATE ALL CIRCUIT NUMBERS WITH PANEL PER COMMENT
 #2.EG NO FAMILY ROOM IN THE SCHEDULE. SEE 408.4 CIRCUIT
 DIRECTORY OR CIRCUIT IDENTIFICATION
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 .
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718