2008-04-19 08:52:00BUILDING PLAN REVIEW
 PERMIT: 08040184
 ADD: 1617 N.FLAGLER DR.
 CONT: KENNETH M. SALVUCCI INC.
 TEL: (561)684-7459
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. /
  
 3)UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 4)1207.3 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 PROVIDE THE MANUFACTURE?S SPECIFICATIONS FOR THE CORK
 SHOWING COMPLIANCE WITH THIS SECTION.
  
 5)SHOW THE NEW LAYOUT OF THE SPRINKLER HEADS IN
 RELATION TO THE NEW CONSTRUCTION. FBC 106.3.5.1.1(5)
  
 6)FBC 907.2.10.1.2 GROUPS R-2, SINGLE- OR
 MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND
 MAINTAINED IN GROUPS R-2, REGARDLESS OF OCCUPANT LOAD
 AT ALL OF THE FOLLOWING LOCATIONS:
 1.ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
 2.IN EACH ROOM USED FOR SLEEPING PURPOSES. THERE IS
 NO SMOKE ALARM IN THE MASTER BED ROOM OR IN THE
 IMMEDIATE VICINITY ON THAT ROOM.
  
 7)907.2.10.3 WHERE MORE THAN ONE SMOKE ALARM IS
 REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING
 UNIT IN GROUP R-2, R-3 OR R-4, OR WITHIN AN INDIVIDUAL
 DWELLING UNIT OR SLEEPING UNIT IN GROUP R-1, THE SMOKE
 ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT. THE ALARM SHALL BE
 CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE
 LEVELS WITH ALL INTERVENING DOORS CLOSED.
  
 8)FOR PLAN REVIEW PURPOSES INDICATE THE TYPE OF
 BUILDING PER TABLE 601 AND 602 OF THE FBC 2004 ALSO THE
 USE AND OCCUPANCY PER CH. 3
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  