2008-04-19 08:52:00 | BUILDING PLAN REVIEW |
| PERMIT: 08040184 |
| ADD: 1617 N.FLAGLER DR. |
| CONT: KENNETH M. SALVUCCI INC. |
| TEL: (561)684-7459 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 4-19-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. / |
| |
| 3)UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE' |
| SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. |
| |
| 4)1207.3 SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| PROVIDE THE MANUFACTURE?S SPECIFICATIONS FOR THE CORK |
| SHOWING COMPLIANCE WITH THIS SECTION. |
| |
| 5)SHOW THE NEW LAYOUT OF THE SPRINKLER HEADS IN |
| RELATION TO THE NEW CONSTRUCTION. FBC 106.3.5.1.1(5) |
| |
| 6)FBC 907.2.10.1.2 GROUPS R-2, SINGLE- OR |
| MULTIPLE-STATION SMOKE ALARMS SHALL BE INSTALLED AND |
| MAINTAINED IN GROUPS R-2, REGARDLESS OF OCCUPANT LOAD |
| AT ALL OF THE FOLLOWING LOCATIONS: |
| 1.ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE |
| SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS. |
| 2.IN EACH ROOM USED FOR SLEEPING PURPOSES. THERE IS |
| NO SMOKE ALARM IN THE MASTER BED ROOM OR IN THE |
| IMMEDIATE VICINITY ON THAT ROOM. |
| |
| 7)907.2.10.3 WHERE MORE THAN ONE SMOKE ALARM IS |
| REQUIRED TO BE INSTALLED WITHIN AN INDIVIDUAL DWELLING |
| UNIT IN GROUP R-2, R-3 OR R-4, OR WITHIN AN INDIVIDUAL |
| DWELLING UNIT OR SLEEPING UNIT IN GROUP R-1, THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| ALARMS IN THE INDIVIDUAL UNIT. THE ALARM SHALL BE |
| CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE |
| LEVELS WITH ALL INTERVENING DOORS CLOSED. |
| |
| 8)FOR PLAN REVIEW PURPOSES INDICATE THE TYPE OF |
| BUILDING PER TABLE 601 AND 602 OF THE FBC 2004 ALSO THE |
| USE AND OCCUPANCY PER CH. 3 |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |