2008-05-08 13:35:14****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.REVISE THE FLOOR PLAN TO SHOW THE LOCATION OF
 WORK.
  
 2. SHOW REQUIRED FIRE RESISTANCE RATING FOR THE WALL
 AND HOW PROPOSED WORK WILL COMPLY.THIS APPEARS TO BE
 A 1 HOUR EXIT CORRIDOR REQUIRED BY FBC TABLE 1016.1.
  
 3.SEE FBC803.3, STABILITY.THE DATA SUBMITTED FOR
 THE LIQUID NAIL STATED THAT HIGH HEAT CONDITIONS ARE TO
 BE AVOIDED.IT DOES NOT APPEAR TO COMPLY WITH THE HEAT
 REQUIREMENTS OF FBC803.3.
  
 4.HOW HAS THE DETERIORATION OF THE EXISTING DRYWALL
 AFFECTED REQUIRED FIRE RESISTANCE?
  
 5.GYPSUM BOARD TO BE INSTALLED INACCORDANCE WITH
 FBC 2508.1.SEE GA 216, A TEST ON THE EXISTING DRYWALL
 IS REQUIRED, SECTION 12.
  
 6.PROVIDE A DETAIL FOR PROPOSED WORK.INCLUDE SIZE
 OF DRYWALL, HEIGHT, TYPE.
  
 7.SEE GA 216, WALLPAPER TO BE REMOVED PRIOR TO
 ADHESION OF NEW DRYWALL.PLEASE NOTE ON THE DETAIL.
  
 8.WHO WILL CERTIFY THE TEST ON THE EXISTING DRYWALL
 AND FIRE RESISTANCE?
  