2008-05-12 08:23:57THIS REVIEW WAS PERFORMED ON PLANS FOR TITLED "CITY
 COMMONS AND WATERFORNT DOCKS, NORTH CLEMATIS DOCK
 UTILITIES.
  
 1. IT DOES NOT APPEAR THAT THE PREVIOUS FIRE RESCUE
 PLANS REVIEW NOTES WERE ADDRESSED BY THESE DRAWINGS.
 PLEASE DISPLAY NEAREST FIRE HYDRANT.
  
 2. THE PORTABLE FIRE EXTINGUISHERS INDICATED ON THE
 PLANS NEED TO BE PROPERLY SERVICED TAGGED.
  
 3. THE REQUIRED SMOKING RESTRICTIONS AS INDICATED IN
 NFPA 303 IS NOT ADDRESSED BY THESE PLANS.
  
 4. THE REQUIRED STANDPIPE SYSTEM SHALL MEET THE
 REQUIREMENTS OF NFPA 303, THE STANDARD FOR MARINAS AND
 BOATYARDS. THE WET CLASS I STANDPIPE SYSTEM SHALL MEET
 THE REQUIREMENTS OF NFPA 14, THE STANDARD FOR THE
 INSTALLATION OF STANDPIPE, PRIVATE HYDRANT, AND HOSE
 SYSTEMS. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE STANDPIPE SYSTEM. THE STANDPIPE
 SYSTEM WHEN INSTALLED SHALL BE PRESSURE TESTED ALONG
 WITH THE PROPOSED FIRE DEPARTMENT CONNECTION (FDC) TO
 ENSURE TIGHTNESS. THE HOSE VALVES SHALL BE EQUIPPED
 WITH 2 1/2 TO 1 1/2 REDUCERS. THE HOSE VALVES AND
 PIOING SHALL BE PROPERLY RESTRAINED.
  
 5. ALL ELECTRICAL SYSTEMS AND DEVICES SHALL COMPLY WITH
 NFPA 70, THE NATIONAL ELECRICAL CODE AND NFPA 303, THE
 STANDARD FOR MARINAS AND BOATYARDS.
  
 6. PLEASE INDICATE THE PORPOSED MEANS OF TRANSMITTING
 OF AN EMERGENCY AT THIS LOCATION. NFPA 303, REQUIRES
 THAT A MEANS TO REPORT AN EMERGENCY SHALL BE PROVIDED
 AND IF THIS MEANS IS A TELEPHONE IT SHALL NOT REQUIRE A
 COIN TO OPERATE.
  
 MIKE CARSILLO, BATTALION CHIEF