2008-05-12 08:23:57 | THIS REVIEW WAS PERFORMED ON PLANS FOR TITLED "CITY |
| COMMONS AND WATERFORNT DOCKS, NORTH CLEMATIS DOCK |
| UTILITIES. |
| |
| 1. IT DOES NOT APPEAR THAT THE PREVIOUS FIRE RESCUE |
| PLANS REVIEW NOTES WERE ADDRESSED BY THESE DRAWINGS. |
| PLEASE DISPLAY NEAREST FIRE HYDRANT. |
| |
| 2. THE PORTABLE FIRE EXTINGUISHERS INDICATED ON THE |
| PLANS NEED TO BE PROPERLY SERVICED TAGGED. |
| |
| 3. THE REQUIRED SMOKING RESTRICTIONS AS INDICATED IN |
| NFPA 303 IS NOT ADDRESSED BY THESE PLANS. |
| |
| 4. THE REQUIRED STANDPIPE SYSTEM SHALL MEET THE |
| REQUIREMENTS OF NFPA 303, THE STANDARD FOR MARINAS AND |
| BOATYARDS. THE WET CLASS I STANDPIPE SYSTEM SHALL MEET |
| THE REQUIREMENTS OF NFPA 14, THE STANDARD FOR THE |
| INSTALLATION OF STANDPIPE, PRIVATE HYDRANT, AND HOSE |
| SYSTEMS. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| INSTALLATION OF THE STANDPIPE SYSTEM. THE STANDPIPE |
| SYSTEM WHEN INSTALLED SHALL BE PRESSURE TESTED ALONG |
| WITH THE PROPOSED FIRE DEPARTMENT CONNECTION (FDC) TO |
| ENSURE TIGHTNESS. THE HOSE VALVES SHALL BE EQUIPPED |
| WITH 2 1/2 TO 1 1/2 REDUCERS. THE HOSE VALVES AND |
| PIOING SHALL BE PROPERLY RESTRAINED. |
| |
| 5. ALL ELECTRICAL SYSTEMS AND DEVICES SHALL COMPLY WITH |
| NFPA 70, THE NATIONAL ELECRICAL CODE AND NFPA 303, THE |
| STANDARD FOR MARINAS AND BOATYARDS. |
| |
| 6. PLEASE INDICATE THE PORPOSED MEANS OF TRANSMITTING |
| OF AN EMERGENCY AT THIS LOCATION. NFPA 303, REQUIRES |
| THAT A MEANS TO REPORT AN EMERGENCY SHALL BE PROVIDED |
| AND IF THIS MEANS IS A TELEPHONE IT SHALL NOT REQUIRE A |
| COIN TO OPERATE. |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |