2008-04-03 16:05:52 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE SUBMITTED PLAN DOES NOT REFLECT THE PERMIT |
| APPLICATION. THE PERMIT APPLICATION INDICATES THAT A |
| NEW WALK-IN TUB IS BEING INSTALLED, HOWEVER THE |
| SUBMITTED PLANS ARE INDICATING A NEW SHOWER. PLEASE |
| CORREALATE THE PLANS WITH THE PERMIT APPLICATION. PER |
| FBC PLUMBING SECTION 401.1 SCOPE AND PER (W.P.B.) |
| SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. THE PRODUCT APPROVAL FOR THE WALK-IN TUB INDICATING |
| THE WALK-IN TUB DIMENSIONS AND OTHER INFORMATION IS NOT |
| LEGIBLE. PER FBC PLUMBING SECTION 401.1 SCOPE AND PER |
| (W.P.B.) SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. THE PRODUCT APPROVAL FOR THE "RELIANCE WATER |
| CONTROLS HEATGUARD TMV2 " DOES NOT INDICATE THAT IT IS |
| APPROVED BY ASSE 1016. PLEASE RESUBMIT WITH APPROVAL OR |
| DELETE. PER FBC PLUMBING SECTION 401.1 SCOPE AND PER |
| (W.P.B.) SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 4. ONLY ONE SET OF PRODUCT APPROVALS WERE SUBMITTED. |
| PER (W.P.B.) SECTION 106.1 SUBMITTAL DOCUMENTS SHALL BE |
| SUBMITTED IN TWO OR MORE SETS WITH EACH APPLICATION FOR |
| PERMIT. |
| |
| 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |