Plan Review Notes For Permit 08040078
Permit Number 08040078
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-05 09:25:34 
  
 DENIED
  
 1)PLEASE SEE THAT THE HEADER/SILL #12 CHOSEN ON PAGE
 2 OF THE PRODUCT APPROVAL AND USED FOR WINDOW
 INSTALLATION PER"A" AND "D" ON PAGE 6 WILL NOT WORK
 FOR THE SILL APPLICATION (PAGE 13 "D" WALL MOUNTING
 COLUMN). THE HEAVY DUTY EXTRUSION #14WILL WORK FOR
 THE BOTTOM IF THE 6'-0" SHUTTER SPAN IS CHOSEN, THE O/C
 SPACING IS 3.5" PLEASE MAKE CORRECTIONS TO THE PRODUCT
 APPROVALS AND SHUTTER SCHEDULE
  
 2)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT
  
 BLDG PLAN REVIEW