2008-04-03 18:32:10RESIDENTIAL WINDOWS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SPECIFYEXISTING TYPE OF WINDOW TO BE REPLACED TO
 VERIFY COMPLIANCE WITH SEC. 501.2 AND 505.1 OF 2004
 EXISTING BUILDING CODE.
 EGRESS OPENINGS CAN'T BE LESS THAN WHAT IT WAS BEFORE.
  
 2- STORM SHUTTERS INSTALLATION SCHEDULE:
 A)DESIGN PRESSURES SPECIFIED ON STORM SHUTTERS ARE
 TOO LOW. PROVIDE ACTUAL CALCULATIONS OR USE TABLE
 R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE AS A
 REFERENCE.
 ***NOTE: TAKE INTO CONSIDERATION THAT SOME OPENINGS ARE
 LOCATED ON END ZONE #5.
  
 B)SHUTTER SPANSHOWN ON COLUMN #6 IS SHOWN
 EXACTLY AS THE WINDOW OPENING HEIGHT.THIS NEEDS TO BE
 REVISED, BECAUSE NEED TO HAVE IN CONSIDERATION THE
 MINIMUM EDGE DISTANCESHOWN ON COLUMN #8. REVISE AS
 REQUIRED.
  
 C) OPENING #3 DOESN'T COMPLY WITH TABLE 2 NOTEON
 SHEET 6 OF 6 OF STORM SHUTTERS DRAWINGS SUBMITTED.
 MINIMUM PANEL LENGTH REQUIRED IS 30". OTHERWISE,
 ENGINEERING CALCULATIONS ARE REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  