Plan Review Notes For Permit 08040047 |
Permit Number |
08040047 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-04-03 18:32:10 | RESIDENTIAL WINDOWS, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- SPECIFYEXISTING TYPE OF WINDOW TO BE REPLACED TO | | VERIFY COMPLIANCE WITH SEC. 501.2 AND 505.1 OF 2004 | | EXISTING BUILDING CODE. | | EGRESS OPENINGS CAN'T BE LESS THAN WHAT IT WAS BEFORE. | | | | 2- STORM SHUTTERS INSTALLATION SCHEDULE: | | A)DESIGN PRESSURES SPECIFIED ON STORM SHUTTERS ARE | | TOO LOW. PROVIDE ACTUAL CALCULATIONS OR USE TABLE | | R301.2(2) OF 2004 FLORIDA RESIDENTIAL CODE AS A | | REFERENCE. | | ***NOTE: TAKE INTO CONSIDERATION THAT SOME OPENINGS ARE | | LOCATED ON END ZONE #5. | | | | B)SHUTTER SPANSHOWN ON COLUMN #6 IS SHOWN | | EXACTLY AS THE WINDOW OPENING HEIGHT.THIS NEEDS TO BE | | REVISED, BECAUSE NEED TO HAVE IN CONSIDERATION THE | | MINIMUM EDGE DISTANCESHOWN ON COLUMN #8. REVISE AS | | REQUIRED. | | | | C) OPENING #3 DOESN'T COMPLY WITH TABLE 2 NOTEON | | SHEET 6 OF 6 OF STORM SHUTTERS DRAWINGS SUBMITTED. | | MINIMUM PANEL LENGTH REQUIRED IS 30". OTHERWISE, | | ENGINEERING CALCULATIONS ARE REQUIRED. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 | | |
|