Plan Review Notes
Plan Review Notes For Permit 08040035
Permit Number 08040035
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-07 14:10:36****************PROVISO****************
 (A) SHEET 4 PLUMBING NOTE #16: AIR CHAMBERS ARE NOT
 APPROVED BY FBC-2004.
 PER FBC PLUMBING SECTION 604.9 WATER HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
  
 (B) SHEET 5 WATER ISOMETRIC RISER: THERMAL EXPANSION
 CONTROL REQUIRED FOR THE WATER HEATER.
 607.3.2 BACKFLOW PREVENTION DEVICE OR CHECK VALVE.
 WHERE A BACKFLOW PREVENTION DEVICE, CHECK VALVE OR
 OTHER DEVICE IS INSTALLED ON A WATER SUPPLY SYSTEM
 UTILIZING STORAGE WATER HEATING EQUIPMENT SUCH THAT
 THERMAL EXPANSION CAUSES AN INCREASE IN PRESSURE, A
 DEVICE FOR CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER