Plan Review Notes
Plan Review Notes For Permit 08040031
Permit Number 08040031
Review Stop B
Sequence Number 2
Notes
Date Text
2008-04-08 09:49:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1)FOR THE FLAT ROOF, SELECT THE APPROVED ASSEMBLY YOU
 ARE USING.ALSO INDICATE WHICH FASTENER YOU ARE USING
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 A POST-IT NOTE WAS PLACED ON PAGE 20, SYSTEM TYPE E2.
 THIS SYSTEM HAS A DESIGN PRESSURE LIMITATION OF -60;
 THEREFORE YOU WOULD NEED ENHANCED FASTENING FOR ZONE 3.
 ONLY THE SYSTEM ON PAGE 22, SYSTEM E4, DOES NOT REQUIRE
 ENHANCED FASTENING AND ENGINEERING AS THE DESIGN
 PRESSURE FOR THIS SYSTEM IS -112.5.
  
 2.)SEE PRODUCT LIMITATION #7.IF ENHANCED FASTENING
 IS REQUIRED, CALCULATIONS PREPARED BY AN ARCHITECT,
 ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED FOR
 ENHANCED FASTENING.
  
  
  