Date Text
2008-04-25 14:36:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1AS AMENDED.
  
 INDICATE COMPLIANCE WITH THE FOLLOWING ON THE PLAN.
 1} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.
  
 2} 225.32 LOCATION.
 THE DISCONNECTING MEANS SHALL BE INSTALLED EITHER
 INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE SERVED
 OR WHERE THE CONDUCTORS PASS THROUGH THE BUILDING OR
 STRUCTURE. THE DISCONNECTING MEANS SHALL BE AT A
 READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTOR
  
 3} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  