Plan Review Notes
Plan Review Notes For Permit 08030728
Permit Number 08030728
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-28 17:14:262004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATIONS TO DETACHED GARAGE
  
 DENIED BY BUILDING 2004 FBC 106.1.2* CITY AMENDMENTS.
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) A SIGNED, SEALED AND DATED COPY OF THE SOIL REPORT
 IS REQUIRED. SEE FS 471.
  
 3) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION
 FOR TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM).
  
 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE .
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 5)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES. CONDENSATE LINES AND ROOF
 DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM)
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS.
 GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL
 PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF
 ABOVE ANOTHER ROOF.
  
 6)SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 7) THE OPENING PRESSURES FOR THE EXTERIOR DOORS LOCATED
 IN WALL ZONE 5 ARE TOO LOW. PLEASE REVISE. SEE TABLE R
 301.2(2).
  
 8) THE WALL SECTIONS SPECIFY R-19 INSULATION IN THE
 EXTERIOR WALLS. THE WALLS ARE SPECIFIED AS 2 X 4 WHICH
 CAN ONLY ACCOMODATE R-11 INSULATION. PLEASE REVISE.
  
 9) TRUSS NOTE (9) ON SHEET A4 NEEDS TO BE REVISED TO
 COMPLY WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL
 SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6
 INCHES ON CENTER AT INTERMEDIATE FRAMING. WHERE ROOF
 FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < 0.49 IS
 USED, SPACING OF RING-SHANK FASTENERS SHALL BE 4 INCHES
 ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR GREATER
 DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1
 .
  
 10) ON SHEET A4 MASONRY NOTES 5 AND 6 SPECIFY THE WRONG
 EDITIONS OF ACI 530, ASCE5, ASCE6, TMS402 AND TMS602.
 THE 2002 EDITION OF THESE STANDARDS ARE REFERENCED IN
 THE 2004 FBC. SEE CHAPTER 43 OF THE 2004 FBC
 RESIDENTIAL.
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR WINDOWS,
 DOORS, OVERHEAD GARAGE DOORS, ROOF COVERING, CONNECTORS
 AND STORM PANELS AS REQUIRED BY DCA RULE 9B-72.
  
 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) NOTE: THE FLOOR PLAN SPECIFIES AN EGRESS WINDOW AND
 A TEMPERED GLASS WINDOW. BASED ON THE PLANS THAT WERE
 SUBMITTED, THESE WINDOWS ARE NOT REQUIRED TO BE EITHER.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]