2008-04-28 17:14:26 | 2004 FBC W/2007 REVISIONS |
| LEVEL 3 ALTERATIONS TO DETACHED GARAGE |
| |
| DENIED BY BUILDING 2004 FBC 106.1.2* CITY AMENDMENTS. |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. |
| |
| 2) A SIGNED, SEALED AND DATED COPY OF THE SOIL REPORT |
| IS REQUIRED. SEE FS 471. |
| |
| 3) SHOW COMPLIANCE WITH FBC R SECTION 704 INSPECTION |
| FOR TERMITES IN ORDER TO PROVIDE FOR INSPECTION FOR |
| TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL |
| COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A |
| BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). |
| |
| 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| GRADE . |
| CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND |
| ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT |
| ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY |
| VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM) |
| ELSEWHERE. |
| |
| 5)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST |
| DECAY AND TERMITES. CONDENSATE LINES AND ROOF |
| DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 MM) |
| AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS. |
| GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| ABOVE ANOTHER ROOF. |
| |
| 6)SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 / |
| 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM |
| OPENINGS. |
| |
| 7) THE OPENING PRESSURES FOR THE EXTERIOR DOORS LOCATED |
| IN WALL ZONE 5 ARE TOO LOW. PLEASE REVISE. SEE TABLE R |
| 301.2(2). |
| |
| 8) THE WALL SECTIONS SPECIFY R-19 INSULATION IN THE |
| EXTERIOR WALLS. THE WALLS ARE SPECIFIED AS 2 X 4 WHICH |
| CAN ONLY ACCOMODATE R-11 INSULATION. PLEASE REVISE. |
| |
| 9) TRUSS NOTE (9) ON SHEET A4 NEEDS TO BE REVISED TO |
| COMPLY WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO |
| 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL |
| SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D |
| RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6 |
| INCHES ON CENTER AT INTERMEDIATE FRAMING. WHERE ROOF |
| FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < 0.49 IS |
| USED, SPACING OF RING-SHANK FASTENERS SHALL BE 4 INCHES |
| ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR GREATER |
| DESIGN WIND SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1 |
| . |
| |
| 10) ON SHEET A4 MASONRY NOTES 5 AND 6 SPECIFY THE WRONG |
| EDITIONS OF ACI 530, ASCE5, ASCE6, TMS402 AND TMS602. |
| THE 2002 EDITION OF THESE STANDARDS ARE REFERENCED IN |
| THE 2004 FBC. SEE CHAPTER 43 OF THE 2004 FBC |
| RESIDENTIAL. |
| |
| 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR WINDOWS, |
| DOORS, OVERHEAD GARAGE DOORS, ROOF COVERING, CONNECTORS |
| AND STORM PANELS AS REQUIRED BY DCA RULE 9B-72. |
| |
| 12) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 13) NOTE: THE FLOOR PLAN SPECIFIES AN EGRESS WINDOW AND |
| A TEMPERED GLASS WINDOW. BASED ON THE PLANS THAT WERE |
| SUBMITTED, THESE WINDOWS ARE NOT REQUIRED TO BE EITHER. |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |